Trane YCZ035F1 Ventilation Hood User Manual


 
Page 21
TROUBLESHOOTING CHART
SYSTEM FAULTS
ELECTRICAL
REFRIGERANT CIRCUIT
P
-PRIMARY CAUSES S-SECONDARY CAUSES
Liquid Pressure Too high
Liquid Pressure Too Low
Suction Pressure Too High
Suction Pressure Too Low
Liquid Refrigerant floodback (TXV System)
Liquid Refrig. floodback (Cap. Tube System)
I. D. Coil Frosting
Compressor Runs Inadequate or No Cooling
Compressor & O.D. fan Do Not Start
Compressor Will Not Start But O.D. Fan Runs
O.D. Fan Won't Start
Compressor Hums But Will Not Start
Compressor Cycles on IOL
I.D. Blower Won't Start
CHECKOUT PROCEDURE
p
IGN LED DIAGNOSTIC INDICATOR
FLASHING SLOW NORMAL CALL FOR HEAT
CONTINUOUS ON NORMAL
CONTINUOUS OFF CHECK POWER / INTERNAL FAILURE
2 FLASHES SYSTEM LOCKOUT ( NO FLAME )
3 FLASHES PRESSURE SWITCH PROBLEM
4 FLASHES HIGH LIMIT (TCO) OPEN
5 FLASHES FLAME SENSED WITH GAS VALVE OFF
6 FLASHES FLAME ROLLOUT SWITCH (FL) OPEN
7 FLASHES W1 & W2 SWAPPED