Trane CG-PRC007-EN Refrigerator User Manual


 
27CG-PRC007-EN
Performance
Data — 60 HZ
Table PD-18— Part Load Data, ARI Points (10-60 Tons)
Entering Condenser Air Temperature (Degrees F)
Model 95 86.9 84.5 77.7 77.3 72.5 72.3 71.5
Tons Number 100% Load 86% Load 82% Load 71% Load 70% Load 62% Load 62% Load 61% Load
EER 10.0
10 CGA 120
2
Capacity (Tons) 8.7
KW Input 10.5
EER 9.6
15 CGA 180 Capacity (Tons) 13.6
KW Input 16.9
EER 9.8 15.2
20 CGAF-C20 Capacity (Tons) 17.7 10.7
KW Input 21.6 8.5
EER 9.8 13.8
25 CGAF-C25 Capacity (Tons) 23.1 16.3
KW Input 28.3 14.2
EER 9.8 14.2
30 CGAF-C30 Capacity (Tons) 28.0 17.0
KW Input 34.3 14.4
EER 9.7 11.9 15.1
40 CGAF-C40 Capacity (Tons) 34.5 28.4 21.4
KW Input 42.7 28.6 17.1
EER 9.7 11.3 13.5
50 CGAF-C50 Capacity (Tons) 43.0 37.2 30.6
KW Input 53.2 39.4 27.2
EER 9.7 11.9 15.2
60 CGAF-C60 Capacity (Tons) 55.4 45.7 34.6
KW Input 68.6 45.9 27.3
Table PD-18 Continued — Part Load Data, ARI Points (10-60 Tons) Continued
Entering Condenser Air Temperature (Degrees F)
Model 66.2 65.3 57.4 55
Tons Number 52% Load 51% Load 37% Load 32% Load
EER 13.5
10 CGA 120 Capacity (Tons) 4.6
KW Input 4.1
EER 13.5
15 CGA 180 Capacity (Tons) 7.1
KW Input 6.2
EER————
20 CGAF-C20 Capacity (Tons)
KW Input
EER 15.3
25 CGAF-C25 Capacity (Tons) 11.7
KW Input 9.1
EER————
30 CGAF-C30 Capacity (Tons)
KW Input
EER 17.6
40 CGAF-C40 Capacity (Tons) 10.9
KW Input 7.4
EER 17.0
50 CGAF-C50 Capacity (Tons) 15.9
KW Input 11.2
EER 18.3
60 CGAF-C60 Capacity (Tons) 17.8
KW Input 11.7
(10–60 Ton)
Part Load
Notes:
1. Rated in accordance with ARI Standard 550/590-98
- 44 Degrees leaving chilled water temperature
- Constant Evaporator waterflow as determined at full load operation, 95 F ambient, and 10F evaporator temperature drop.
- Entering ambient temperature based on 55F for loads below 33%
- Entering ambient temperature based on 0.60(%load)+35 for loads above 33%
- EER- Energy Efficiency Ratio ( Btu/Watt-hour). Power inputs include compressor, condenser fans and control power.
2. Single phase CGA120B1 model should be re-rated at all operating points using the following factors: 1.08 x KW, 0.92 x EER