Zephyr COK-E36SX Ventilation Hood User Manual


 
5
Installation - M ounting Height & Clearance
DUC T I N G
36"
Min 96"-Max 124
Min 28"-Max 36"
Min 32"-Max 52"
14 1/2"
Minimum mount height between range top to hood bot-
tom should be no less than 28".
Maximum mount height should be no higher than 36".
It is important to install the hood at the proper mounting
height. Hoods mounted too low could result in heat
damage and re hazard; while hoods mounted too high
will be hard to reach and will loose its performance and
eciency.
If available, also refer to range manufacturer's height
clearance requirements and recommended hood
mounting height above range. Always check your local
codes for any differences.
A minimum of 6” round or 3-1/4 x 10"
rectangular duct work must be used to maintain
maximum air ow eciency with the 600 cfm
internal blower. A minimum of10"to 8” round
must be
used with the 1000 cfm external blower.
Always use rigid type metal duct work only.
Flexible ducts could restrict air ow by up
to 50%.
Use calculation worksheet to compute total
duct work.
ALWAYS, when possible, reduce the number
or transitions and turns. If a reducer is used,
install a long reducer instead of a pancake
reducer. Reduce duct size as far away from
opening as possible.
If turns or transitions are required:
Install as far away from opening and as far
apart, between 2, as possible.
Minimum Duct Size:
Round - 6” minimum at 600 cfm
Round - 10" to 8” minimum at 1000 cfm
Rect angular - 3 1/4” x 10” minimum only if
using internal blower at 600 cfm. Using
rectangular ductwork will require a transition
adapter (not provided, but readily available at
most hardware stores).
DAMAGE-SHIPMENT / INSTALLATION:
Please fully inspect unit for damage
before installation.
If the unit is damaged in shipment , return
the unit to the store in which it was bought
for repair or replacement.
If the unit is damaged by the customer ,
repair or replacement is the responsibility
of the customer.
If the unit is damaged by the installer (if
other than the customer), repair of replace
ment must be made by arrangement
between customer and installer.
*Minimum ceiling height of 96”. Hood
mounted at 28” above cooking surface.
**Maximum ceiling height of 124". Hood
mounted at 36" above cooking surface.