Line Voltage Requirements
Line voltage must not exceed rated voltage. See rating plate
attached to range for kilowatt rating. Line voltage less than
rated voltage will result in slow heating. Wiring system must
conform to Underwriters Laboratories, Inc. standards and
National Electrical Code. Installation must conform to all
local, municipal and state building codes, and local utility
regulations. Range must be connected only to a supply
circuit as specified on rating plate wiring diagram of range.
ART6511 requires 3 wires, 120/240 Volts, 60 Hertz A.C.
ARR6400 can use 120/208 or 120/240 Volts. House
wiring and fusing must comply with local wiring codes. If
no codes apply, wire according to National Electrical
Codes.
Power Supply Location
Shaded area show range clearance for electrical
connection. (Figure 4)
A
B
C
D
A
E
A—3 inches
B—7 inches
C—6 inches
D—30
1
/8 inches minimum
E—24
1
/16
Figure 4
Power Cord Requirements
Power cord is not supplied with range. Power cord must
be U.L. Listed and meet NEC and Mobile Home
Manufacturers Association Standards. Cord must be
rated at a minimum 250V—40 AMP, equipped with a
plug configuration in accordance with NEMA. Conductors
must end with closed loop (ring) terminals at the range.
Three-conductor cord plug NEMA 10-50P allowed for
residential.
Four-conductor cord plug NEMA 14-50P required for
most mobile home installations but can be used for
residential.
NOTE: Only a power cord suitable for use with ranges may
be used. For installation in a mobile home, or area where
local codes do not permit grounding through the neutral
terminal, a 4-wire cord must be used.
Range Terminal Block
See Figure 5. Connection block is located at bottom rear
of range behind rear cover panel. Remove rear cover
screw. Directly below terminal block is a hole for a power
supply service cord. Power cord is not supplied with
range.