PROGRAMMABLE PARAMETERS FOR SOFTWARE
The programmable parameters with their factory defaults described in this section. Table on page 17 contains the parameter
codes along with their permitted values and default settings. Parameters P1 / t-1 through t-5 are user adjustable parameters.
Checking Software Revision Level
To confirm software revision, first turn off power to unit. Then, observe when power is reapplied: The display will light all LEDs
for 2 seconds, the display will go blank for 1 second, then the display will show the software revision (C-19) for 2 seconds.
Entering And Using Program Mode
• While in the Off mode, enter program mode (P) by pressing and holding both the On/Off and Function buttons for 5
seconds.
• Then, to enter the (T) programming mode to make changes, push and hold the RESET SWITCH on the control box for
15 seconds until the t-1 appears.
•Use the On/Off button to advance through parameters. Use the Function button to select the parameter value
desired.
• Exit the program mode either by pressing and releasing both the On/Off and Function buttons or by waiting 60
seconds.
PROGRAM PARAMETER DESCRIPTIONS
P-1: t-1: High Pressure Restart Delay - This sets the start compressor restart delay after a high refrigerant pressure fault is
cleared. The default setting is 0 and can be set from 0-30 minutes. Default "0" for off is mainly used for sport fishing where
backing down can cause an airlock. Only use for continuous nuisance trips.
t-2: Low AC Line Voltage - This option can be set to detect low AC line voltage. Low AC line voltage condition must exist for 5
minutes for a shtudown to occur. Default setting is off and can be set from 75 to 100 (for 115VAC) or 175 to 200 (for 230VAC).
t-3: CAN ID - Used to set CAN bus ID. The range is from 1-254.
t-4: CAN Group ID - Used to set CAN bus group ID. The range is from 1-254.
t-5: Reset Programmable Parameters - Resets all programmable parameters to factory defaults. Set this setting to 1 and unit
will reset all values. Setting will change back to 0 on exit of the programming mode or by pressing the On/Off button to scroll
through parameters.
NOTE
Changes to technical parameters not listed above should be performed by an authorized service dealer. Please
contact Dometic at 800-542-2477 for a dealer near you.
PROGRAM PARAMETER DEFAULT SETTINGS
Table 3 shows the default setting of each programmable parameter.
Table 3: Programmable Parameters - Values and Defaults
Number Description Default Value Range
P-1
t-1
High Pressure Restart Delay
0
0 - 30 minutes
t-2
Low AC Line Voltage off 75-100 or 175-200
t-3 CAN ID
n/a 1-254
t-4 CAN Group ID 5 1-254
t-5
Reset Programmable Parameters
0
0 = No, 1 = Yes