EMI Volts/HZ/pH Ventilation Hood User Manual


 
www.enviromaster.comSide Discharge Condensers
22
MOUNTING DIMENSIONS
Model Size A B C D
S1C/S1H
9,
S1C/S1H
2
4 ⅝” 14
11
/
16
3” 12
7
/
16
S1C/S1H
8,
S1C/S1H
2
4 ⅝” 22
11
/
16
3” 12
7
/
16
S1C
3,
S1C
6
7” 23
15
/
16
3” 12
7
/
16
Easy access interconnects
on back of unit
1/2” Diameter Lag Holes
A
A
B
D
C
SOUND DATA
Size Btuh
dBA
Heat
Pump &
Cool
09 59
1
2 59
1
8 62
2
4 63
Cool
Only
30 68
3
6 68
S1C/S1H SPECIFICATIONS AND DIMENSIONS
SHIPPING WEIGHT
Size Btuh
Lbs.
9-12 98
18-24
156
30-36
210
A
B
C
Electrical
connections
PHYSICAL DIMENSIONS
Model Size A B C
S1C/S1H
9 24" 15" 36"
S1C/S1H
2 24" 15" 36"
S1C/S1H
8 32" 15" 36"
S1C/S1H
4 32" 15" 40"
S1C/S1H
3 38” 15” 44”
S1C/S1H
6 38” 15” 48”
SOUND DATA
Model Size
dBA
99 64
22 65
92 65
PHYSICAL DIMENSIONS
Model Size S2C A B C
99 32" 15" 36"
22, 92 32" 15" 40"
SHIPPING WEIGHT
Model Size
Lbs.
99
129
22
167
92
157
S2C ELECTRICAL SPECIFICATIONS
Capacity Volts/HZ/Phase
Fan Mtr.
Compressor
Total
AMPS
MCA
HACR
BRKR
Min.
Volt
Circuit #1 Circuit #2
AMPS HP RLA LRA RLA LRA
9900 208-230/60/1 0.8 0.125 3.5 19 3.5 19 7.8 8.7 15 197
9200 208-230/60/1 0.8 0.125 3.5 19 4.5 21 8.8 10.0 15 197
2200 208-230/60/1 0.8 0.125 4.5 21 4.5 21 9.8 11.0 15 197
MOUNTING DIMENSIONS
Model Size S2C A B C D
99, 92, 22
4 ⅝” 22
11
/
16
3” 12
7
/
16
S2C SPECIFICATIONS AND DIMENSIONS
NOtE: All EMI products are subject to ongoing development. Design and specications may change without notice.
Circuit Designators: 9 = 9,000 Btuh • 2 = 12,000 Btuh
ex. - Model 9200 consists of one 9,000 Btuh compressor and one 12,000 Btuh compressor
Always refer to the rating plate for Minimum Circuit Ampacity on all multiple compressor units