EMI Volts/HZ/pH Ventilation Hood User Manual


 
www.enviromaster.com
Side Discharge Condensers
9
INSTALLATION INSTRUCTIONS
REFRIGERANT PIPING
Continued
2. Protect the valves by wrapping with a
wet rag "heat sink" before brazing.
3. We recommend the use of a shield (can
be made from some scrap metal) to
protect the paint.
4. Braze tubing into ttings.
1. Clean the ends of tubing and insert into
ttings.
5. Attach manifold set.
6. Evacuate line to 500 microns or less to
ensure all moisture has been removed
and there are no leaks.
Refrigerant
Refer to Refrigerant
Charge Table for
specied line charge.
7. Once certain of a good evacuation and
leak free joints, back-seat the valves
(counter-clockwise) to open and allow
factory charge to ll lines and indoor unit.
S1C
Shown
S1C
Shown
S2C
Shown
S1C
Shown
S1C
Shown
Manifold
Vaccum Pump Micron Gage
Manifold Setup For Evacuation
S1C
Shown
S2C