Controller application setting parameters
Para- Controller
Min. Max. Factory Actual
Setting and read-off parameters meter application no.
value value setting setting
codes
1234
1
) The compressor relay closes when the room temperature exceeds
the setting value and differential.
2
) Alarm is released and sensor failure is indicated, if the room
temperature reaches 5°C or more outside the setting range
60° to +50°C.
3)
The frequency is measured after approx. three days and
nights operation after start of the plant (72 cyclings)
otherwise:
ON-time = c03 × 20: 100 minutes
OFF-time interval 20 minus ON-time per minute
4
) Function possibilities with SPDT contact, connected to the
terminals 3 and 4 are the following:
Door alarm
: If SPST is cut out, alarm signalling starts and the fan is
stopped, cf. A04 or F02.
Defrost:
If SPST is cut in, defrost starts. (However, if d03 is not OFF,
defrost will during contact break down start with the programmed time
intervalles).
Bus
: With installed communication card, the position of the SPST
contacts will be registered in the BUS system.
Temperature controller,Temperature -60
o
C50
o
C3
o
C
Thermostat
Differential
1
) r01 0.1 K 20 K 2 K
Max. limitation of set temperature r02 -59
o
C50
o
C50
o
C
Min. limitation of set temperature r03 -60
o
C49
o
C -60
o
C
Adjustment of temperature indication r04 -20 K 20 K 0.0 K
Temperature unit (°C/°F) r05
o
C
Alarm
Upper deviation (above temp. setting + differential
2
) A01 0 K 50 K 5 K
Lower deviation (below temp. setting
2
) A02 0 K 50 K 5 K
Temperature alarm delay A03 0 min 90 min 30 min
Door alarm delay A04 0 min 60 min 30 min
Compressor
Min. ON-time c01 0 min 15 min 0 min
Min. OFF-time c02 0 min 15 min 0 min
Cut-in frequency on sensor fault
3
) c03 0 % 100 % 0 %
Defrost
Defrost method (EL/GAS) d01 EL
Defrost stop temperature d02 0
o
C25
o
C6
o
C
Interval between defrost starts d03 OFF 48 hour 8 hour
Max. defrost duration d04 0 min 180 min 45 min
Time staggening on defrost cut-ins at start-up d05 0 min 60 min 0 min
Drip-off time d06 0 min 20 min 0 min
Fan start delay after defrost d07 0 min 20 min 0 min
Fan start temperature d08 -15
o
C0
o
C-5
o
C
Fan cut-in during defrost (yes/no) d09 yes
Defrost sensor (yes/no) d10 yes
Temperature alarm delay after defrost d11 0 min 199 min 90 min
Fan
Fan stop on compressor cut-out (yes/no) F01 no
Fan stop delay F02 0 min 15 min 0 min
Miscellaneous
Delay of output signal cancellation after start-up o01 2 s 120 s 2 s
Digital input signals
4
)
(0 = not used, 1 = door alarm, 2 = defrost, 3 = bus)
o02 0
Real time clock (if fitted)
Six start times for defrost
All can be cut out by setting on OFF
t01 t06 0 23 OFF
Hour setting t07 0 hour 23 hour 0 hour
Minute setting t08 0 min 59 min 0 min
Fault code display Alarm code display
Fault in controller E 1 High temperature alarm A 1
Disconnected room sensor E 2 Low temperature alarm A 2
Short-circuited room sensor E 3 Door alarm A 4
Disconnected defrost sensor E 4 Status code display
Short-circuited defrost sensor E 5 ON-time S 2
OFF-time S 3
Drip-off time S 4