ASSEMBLY
3.3 Hydraulic Boiler to Tank Connections Kit (BH46)
Connection kit BH46, provides connections from the tank to the
boiler.
The kit consists of
- A pump with cable 3
- Insulated flexible connector 13, length 1120mm
- Insulated flexible connector with elbow 12, length 1200mm
- A bag containing:
- An antisyphon valve 10
- Connecting union 4
- Tee with union nut 1
- Tee 7
- Tee with tappings 9
-3 X
1
/2" plugs 11
- 3 X 1
1
/2" O rings 5
-5 X
3
/4" O rings 14
- 4 X plastic plugs 15
- Flexible clip 16 with fixing 17
IMPORTANT
- Ensure access to pump speed control and vent screw V
- Ensure flexible connectors are run to prevent air pockets
- The
1
/2" plug 11 fitted to Tee 1 can be replaced by a drain cock
- To ensure best venting of the assembly and continued good
operation of the installation, an automatic vent (P) not supplied,
should be fitted on Tee 9 (
1
/2")
- Screw the Tee with union nut 1 and plug 2 on tank outlet D
- Fit the pump 3 to union nut 4 and Tee 1 inserting O rings 5
- Screw Tee 7 to boiler return B
- Screw Tee with tappings 9 with plug 11 to boiler flow A
- Screw valve Tee 10 with plug 11 to tank inlet C
- Connect elbow flexible 12 (1200mm) between 7 & 4 and flexible
13 (1120mm) between 9 & 10 inserting O rings 14.
- Assemble flexible clip 16 and fitting 17 then clip them in the
7.5mm hole E on the boiler rear panel.
- Fit flexible 13 in clip 16.
The pump cable allows simple connection to the boiler control
box. See Electrical section for further information.