Buccaneer GT, Falcon GTE - Installation, Assembly & Servicing
3
1.1 Technical Specifications of Combination Boilers
Boiler:
Maximum operating pressure : 4 bar
Maximum operating temperature : 100ºC
Maximum safety temperature of
boiler (as per TRD 702) : 120ºC
Boiler thermostat setting : 30 - 85ºC
Safety thermostat setting : 110ºC
MLS Calorifier:
Primary circuit (heating water)
- Maximum operating temperature : 95ºC
- Maximum operating pressure : 12 bar
Secondary circuit (domestic hot water)
- Maximum operating temperature : 95ºC
- Maximum operating pressure : 10 bar
Bucaneer GT - Domestic Hot Water Production 3 4 5
MLS tank capacity litres 150 150 150
Continuous flow rate (1) (2) litres/h 640 780 780
Maximum flow rate over 10mn (1) (2) (3) litres/10mn 235 260 260
Weight (Boiler and tank) kg 228 256 284
Falcon GTE - Domestic Hot Water Production 4 (150/250) 5 (150/250)
MLS tank capacity litres 150/250 150/250
Continuous flow rate (1) (2) litres/h 780/950 780/950
Maximum flow rate over 10mn (1) (2) (3) litres/10mn 260/380 260/380
Weight (boiler and tank) 150 litre kg 354 395.5
Weight (boiler and tank) 250 litre kg 384 425.5
(1) Domestic cold water at 10ºC - Domestic hot water at 45ºC - Primary at 80ºC
(2) Storage temperature : 60ºC
(3) Boiler temperature : 80ºC - Ambient temperature : 20ºC
Tank Details
Note: With IDEAL boilers, the setting limits the temperature of the primary circuit at the beginning to 75ºC (adjustment is possible from
50ºC to 95ºC).
Tank Type MLS 150/III MLS 250/II
Primary circuit (central heating water)
Water capacity of coil litres 5.9 7.2
Exchange surface of coil m
2
0.92 1.2
Secondary circuit (sanitary water)
Water capacity litres 150 250
Delivery weight kg 100 130