Miele 10 093 470 Ventilation Hood User Manual


 
Installation
29
f
When installing the cooker hood with a DAR 3000 drop-down frame, make sure
that you no
te the different wall unit height (please refer to the dimensions given
in the DAR 3000 building-in diagram).
* The cooker hood can also be installed in a 600 mm wide unit (a DAR 3000 drop-
down fr
ame cannot be used in this instance).
Safety distance between hob and cooker hood (S)
When planning the installation height of your cooker hood, the minimum safety
distance
between the top of a cooker or hob and the bottom of the cooker
hood is as follows, unless a greater distance is specified by the manufacturer of
your cooking appliance.
See "Warning and Safety" instructions for further information.
Cooking appliance Minimum distance S
Electric hob 450 mm
Electric grill, deep fat fryer (electric) 650 mm
Multi-burner gas hob,
t
otal output 12.6 kW, no burner > 4.5 kW
650 mm
Multi-burner gas hob,
t
otal output > 12.6 kW and 21.6 kW,
no burner > 4.8 kW.
760 mm
Multi-burner gas hob,
t
otal output > 21.6 kW,
or multi-burner gas hob where one burner > 4.8 kW.
Not possible
Single burner gas hob, output 6 kW. 650 mm
Single burner gas hob, output >
6 kW and 8.1 kW.
760 mm
Single burner gas hob, output >
8.1 kW
Not possible
If you are fitting a front panel made of wood or plastic to the cooker hood,
obser
ve the safety distances given by the hob manufacturer regarding the use
of easily flammable materials.