Miele 10 118 580 Ventilation Hood User Manual


 
Installation
31
Distance between cooktop and ventilation hood (S)
Provided a larger distance is not given by the manufacturer of the cooktop,
foll
ow the minimum safety distances between a cooktop and the bottom of the
hood.
Please also observe the information contained in the "IMPORTANT SAFETY
INS
TRUCTIONS" section.
Minimum distance S
Cooking appliance Miele range Non-Miele
r
ange
Electric Cooktops 24" (610 mm)
Electric Barbeques and Fryers 26" (660 mm)
Multiburner Gas Cooktops
43,000 B
TU/hr (12.6 W),
no burner > 15,000 BTU/hr (4.5 kW).
26" (660 mm) 30" (760 mm)
Multiburner Gas Cooktops
73,800 BTU/hr (21.6 W),
no burner > 16,500 BTU/hr (4.8 kW)
30" (760 mm)
Multiburner Gas Cooktops
> 73,800 B
TU/hr (21.6 W),
or one of the burners > 16,500 BTU/hr (4.8 kW)
Not possible
Single Burner Gas Cooktops
20,500 B
TU/hr (6 kW)
26" (660 mm) 30" (760 mm)
Single Burner Gas Cooktops
> 20,500 B
TU/hr (6 kW)
27,600 BTU/hr (8.1 kW)
30" (760 mm)
Single Burner Gas Cooktops
> 27,600 B
TU/hr (8.1 kW)
Not possible
The fully lowered canopy must not go below the minimum distances given.
The height range for the appliance can be extended or limited by moving the
limit switch (see "Installation").