Pitco Frialator L22-355 Fryer User Manual


 
Spin Fryer I12 Cooking Computer
Pitco P/N 60149505
Page 23 of 28 L22-355 Rev 1
6 Other Displays:
Open probe detection is standard on all Pitco
controls. If probe is detected open, normal
heating and cooking activities are suspended.
This display warns operators that the vat
temperature has exceeded set temperature by
+40°F (+22°C), or an absolute maximum of
410°F (210°C). The alarm will also sound. This
display does not show the status of the
mechanical high limit switch.
This message indicates that the drain valve has
been opened, the vat is assumed to be empty by
the controller. Normal heat control activities are
suspended. Display will show an alternating
message [DRAINING] / [TURN OFF]. To restore
to normal operation, close the drain value.
Display will show [TURN OFF].
Turn controller off, and refill the vat. Continue
with normal operations at section 1.
This message indicates that the heating system
failed to respond. Typically, the high
temperature limit switch has tripped and is in
need of resetting. In the case on gas fired
appliances, this message will display if the pilot
fails to light or is detected marginal by the
ignition module. Display will show an alternating
message [HEAT] / [FAILURE].
This message indicates a shorted probe. If probe
is detected as a short circuit, normal heating and
cooking activities are suspended. Display will
show an alternating message
[SYSTEM] / [FAILURE].
This message indicates that a recoverable
system error has occurred. Press ‘6’ for YES to
perform a factory reset or ‘0’ for NO to return to
OFF. Normal use of the system will only resume
when a factory reset has been performed.
Display will show an alternating message
[FACTORY] / [RESET].