Trane 1500 CFM Ventilation Hood User Manual


 
UV-SVN03D-EN 7
Table G1: VUVE general data
Unit Location and Clearances
Locate the unit in an indoor area. The
ambient temperature surrounding the
unit must not be less than 45°F. Do not
locate the unit in areas subject to
freezing.
Attention should be given to service
clearance and technician safety. The
unit should contain enough space for
Description Unit Size
0750 1000 1250 1500
Unit Length w/o end covers (inches)
69 81 93 105
Unit Depth - Standard (inches)
16 5/8 16 5/8 16 5/8 16 5/8
Unit Depth - with false back (inches)
21 1/4 21 1/4 21 1/4 21 1/4
Unit Height - Standard (inches)
30 30 30 30
Shipping Weight (Lbs.)
320 405 450 470
Nominal Filter Size and
14 x 20 x 1 (2) 14 x 24 x 1 (1) 14 x 20 x 1 (2) 14 x 24 x 1 (2)
Quantity (inches)
14 x 30 x 1 (1) 14 x 24 x 1 (1) 14 x 30 x 1 (1)
Dynamic Air Filter Nominal
7 x 42 x 1 (1) 7 x 54 x 1 (1) 7 x 66 x 1 (1) 7 x 78 x 1 (1)
Size (inches) & Qty.
Drain Connection Size (inches)
7/8 ID Hose 7/8 ID Hose 7/8 ID Hose 7/8 ID Hose
Fan Type / Quantity
FC / 2 FC / 2 FC / 4 FC / 4
Motor Data
Quantity 1 1 2 2
Horsepower (ea) 1/4 1/4 1/10 1/10
Number of Fan Speeds (Standard)
3 3 3 3
If DX or electric heat used 1 1 1 1
Number of Fan Speed (ZN520)
3 3 3 3
If exhaust fan or ERSA used 2 2 2 2
If DX or electric heat used 1 1 1 1
Coil Volume (gal.)
Coil Type A 0.178 0.228 0.277 0.327
B 0.311 0.410 0.510 0.610
C 0.311 0.410 0.510 0.610
D 0.444 0.571 0.704 0.931
E 0.444 0.571 0.704 0.931
F 0.610 0.809 1.014 1.213
G 0.610 0.809 1.014 1.213
H 0.395 0.593 0.742 0.837
service personnel to perform mainte-
nance or repair. Provide sufficient
room to make water, and electrical
connection(s). Local and national
codes should be followed in providing
electrical power connections. A 36"
clearance at the unit front is sufficient
for maintenance and service of the
equipment.
Dimensions/Weights/
Clearance
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in death or serious injury
or possible equipment or property-only damage.
!