Vulcan-Hart ML-52947 Range User Manual


 
24
REGULATOR CHECK, ADJUSTMENT, INSTALLATION (Cont.)
2. With only two open top burners ON, note the manometer reading. The reading should be 3.7" Water Column for
natural gas units and 10.0" Water Column for propane gas units. If readings taken are lower, check the incoming line
pressure. NOTE: The line pressure should never drop below 5.0" Water Column for natural gas or 11.0" Water
Column for propane gas.
If line pressure is incorrect, it must be adjusted in order to properly operate the unit. If the line pressure is good, then
the regulator requires adjustment (refer to procedures for regulator adjustment).
If, after the regulator adjustment has been made, the 3.7" water column (natural gas) or 10.0" water column (propane
gas) still is not being maintained, replace the regulator.
3. With the regulator now reading 3.7" Water Colum (natural gas) or 10.0" Water Column (propane gas), turn two open
top burners ON.
4. Recheck the pressure reading. The reading should not fluctuate more than ± .10". If reading is not within tolerance,
replace the regulator.
NOTE: When the burners are OFF, if the pressure reading climbs to an outlet regulator pressure stated in Step 2, check
the regulator vent for obstruction (Figs. 24 & 25).
Fig. 24
Fig. 25
Check also for gas leak at vent. If vent is leaking gas, replace the regulator.
REGULATOR ADJUSTMENT
TOOLS REQUIRED: Flat blade screwdriver, manometer, and 6" adjustable wrench.
NOTE: Before making a regulator adjustment, always verify that the incoming line pressure is correct. The required
incoming minimum line pressure for the Restaurant Range series is 5.0" for natural gas and 11.0" for propane gas. If the
line pressure is not correct, it must be rectified or the unit will not properly operate or achieve proper regulator
adjustment. Also, the regulator must be attached to the unit in the horizontal position with the arrow pointing in the
direction of the gas flow (see Fig. 7).