Xantrex Technology 815-3012 Microwave Oven User Manual


 
80 Freedom SW Owner’s Guide
Troubleshooting
Table 4 provides a detailed description of the detected warning messages and solutions. If you are unable to resolve the problem after
referring to this table, contact your dealer or Customer Service.
Table 4
Detected Warning Messages
Fault
Number Message Fault Type Cause Solution
W48 DC under voltage
(Warning)
Automatic Voltage at the DC input
terminals is below the Low
Battery Cut Out (LBCO)
setting.
Check for the correct battery voltage at the
inverter's DC input terminals.
Check for external DC loads on the
batteries.
Check condition of batteries and recharge
if necessary.
Reduce the Low Battery Cut Out (LBCO)
setting.
Battery bank capacity may be inadequate
for the loads in the system.
W69 AGS not connected Automatic The GenSup Mode setting
is enabled but there is no
AGS connected in the
Xanbus network.
Install a Xanbus AGS on the network or
disable the GenSup Mode setting.
Freedom SW 3K2K InvChg Owners Guide.book Page 80 Thursday, July 31, 2014 1:42 PM