975-0082-01-01 17
Xanbus Automatic Generator Start Installation
Type 3
Type 3 is a three-wire GlowStop with shutdown bypass configuration. The
configuration shown in Figure 9 uses a shutdown bypass output to
temporarily disable the generator’s low oil pressure shutdown functionality
during cranking. Generators with this functionality often have a manual
means of disabling it during cranking.
Figure 9
Type 3 Connection Diagram
Relay Function Preset Configuration Setting
Relay 1 mode GlowStop/Shutdown bypass
Relay 3 mode Preheat/Shutdown bypass
Gen Run signal hold time 0.5 s
Preheat time 20 s
AGS Harness Wires Generator Wires
14
13
12
18
17
16
Relay 1
Relay 2
5A fuse
5A fuse
GENERATOR RUN SIGNAL
START
PREHEAT
STOP
BYPASS SHUTDOWN
GENERATOR RUN SIGNAL RETURN
For additional information, see “Circuit Limitations” on page 11.
Preheat to crank delay 0 s
Crank time 15 s
Crank retry time 30 s
Gen Cool Down 30 s
Gen Spin Down 3 s
Shutdown bypass time 10 s
Start tries 3
Relay Function Preset Configuration Setting