Xanbus Automatic Generator Start Installation
Type 11
Type 11 is a two-wire run mode configuration. It requires only two wires
and one relay to control the generator. Relay 1 closes momentarily once to
start the generator, and closes momentarily again to stop the generator.
Figure 19
Type 11 Connection Diagram
Relay Function Preset Configuration Setting
Relay 1 mode MomentaryRun
Relay 3 mode No function
Gen Run signal hold time 0.5 s
Preheat time 0 s
Preheat to crank delay 0 s
Crank time 10 s
Crank retry time 15 s
Gen Cool Down 30 s
AGS Harness Wires Generator Wires
16
14
13
12
Relay 1
5A fuse
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN
For additional information, see “Circuit Limitations” on page 11.
Gen Spin Down 3 s
Shutdown bypass time 0 s
Start tries 3
Relay Function Preset Configuration Setting