Xanbus Automatic Generator Start Installation
Type 5
Type 5 is a three-wire StartStop configuration that uses relay 3 to provide a
15-second preheat signal.
Figure 11
Type 5 Connection Diagram
Relay Function Preset Configuration Setting
Relay 1 mode StartStop
Relay 3 mode Preheat
Gen Run signal hold time 2 s
Preheat time 15 s
Preheat to crank delay 2 s
AGS Harness Wires Generator Wires
18
17
16
14
13
12
20
19
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY+
Relay 1
Relay 3
Relay 2
5A fuse
5A fuse
5A fuse
GENERATOR RUN SIGNAL
STOP/PREHEAT
START
GENERATOR RUN SIGNAL RETURN
For additional information, see “Circuit Limitations” on page 11.
Crank time 15 s
Crank retry time 15 s
Gen Cool Down 30 s
Gen Spin Down 3 s
Shutdown bypass time 0 s
Start tries 3
Relay Function Preset Configuration Setting