A SERVICE OF

logo

72 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Troubleshooting
Fault Reference Table
When the AGS detects a fault condition, it stops the generator. The red
Fault light also comes on, and the Xanbus System Control Panel (SCP)
displays a fault message.
The AGS remembers the GenMode that it was in at the time it detected the
fault. After you have cleared the fault, the AGS returns to its last known
GenMode.
Table 7
AGS Fault Messages
Fault
Number
Message Self-clearing? Cause Action
F200 Exceeded
max number
of start tries.
Check gen,
clear fault.
No The AGS has tried and
failed to start the
generator. To prevent
draining the start
battery, the AGS will
suspend further start
attempts.
Check the generator’s
fuel level and start
battery condition.
Consult generator
manual.
Clear fault on System
Control Panel screen to
allow retry.
F201 Unable to
stop gen.
Stop gen via
its control
panel.
No The AGS has lost
contact with the
generator or the
generator did not stop
after the AGS sent it a
stop signal.
Change the AGS mode
to Manual Off.
If this fails to work,
stop the generator with
the external stop
switch.
Check generator.
Return AGS to
automatic mode to
resume automatic starts
and stops.
F203 Manual Off:
Gen stopped
by ext
sensor. Reset
GenMode.
No An external sensor
connected to the AGS
has stopped the
generator and put the
AGS into Manual Off
mode.
After the sensor
connected to the
external shutdown has
deactivated, clear the
fault and reset the AGS
to the desired mode.
F500 Serial
Number
Failure,
Service
Required.
No The silicon serial ID
number has failed and
the AGS has gone into
Standby.
Call your dealer or
Xantrex Technology
USA Inc.
F501 Memory
Failure.
Service
Required.
No The AGS has suffered a
non-volatile memory
failure.
Call your dealer or
Xantrex Technology
USA Inc.
F505 Internal
Failure.
Service
Required.
No A controller fault has
occurred and the AGS
has gone into Standby.
Clear the fault. If the
fault persists, call your
dealer or Xantrex
Technology USA Inc.
Table 7
AGS Fault Messages
Fault
Number
Message Self-clearing? Cause Action