CHECK 3 - CHIMNEY CROWN CONDITION.
Damage from condensate usually shows up first in the crown. If
any of the following trouble signs are present, the condition of
the crown is not satisfactory:
a) Crown leaning
b) Bricks missing
c) Mortar missing
d) Tile liner cracked
e) No tile liner
f) Salt staining at mortar joints. (White stains, and mortar
becomes sandy and/or erodes.)
For problems a, b, or c, see Fix 3. If problems d, e, or f are
present, see Fix 4. IMPORTANT: It may be necessary to follow
both Fix 3 and Fix 4.
CHECK 4 - DEBRIS IN CLEANOUT
A cleanout (dropleg) must be present such that the upper edge
of the cleanout cover is at least 12 inches below the lower edge
of the lowest chimney inlet opening.
A chimney without a cleanout could become partially blocked by
debris. If no cleanout is present, the chimney must be refined
(Fix 4). Remove the cleanout cover, and examine the cleanout for
debris. If significant amounts of any of the following are found:
Fuel oil residue
Bricks
Mortar or sand
Pieces of the tile liner
Rusted pieces of the metallic liner - reline the chimney
(Fix 4).
CHECK 5 - LINER CONDITION.
If a metal liner is present, it must be checked. It cannot be
assumed that all existing metal liners are correctly installed and
in good condition.
Remove the lowest existing vent connector, and examine the
inside of the elbow or tee at the base of the liner. A small amount
of soot may be considered acceptable, provided the installer
vacuums it away. If rusted pieces of the liner have collected here,
the metal liner must be removed and replaced (Fix 4).
Next, gently tap the inside of the liner with a Phillips screwdriver.
If the screwdriver perforates the liner, or if the tapping does not
sound like metal hitting metal, the liner must be removed and
replaced (Fix 4).
Remember that all appliances must be vented inside the liner.
Venting one appliance inside the liner and another appliance
outside the liner is not acceptable.
Next, use a flashlight and small mirror to sight up the liner. B vent
must be supported so as to not come into direct contact with the
chimney walls or tile liner. If it is not, it can probably be rehung so
as to be acceptable. A thimble or fire stop may be helpful here.
Flexible liners should be hung straight or nearly straight. If it is
spiraled in the chimney and in good condition, it should be
rehung. To do this, break the top seal; pull up and cut off the
excess liner length, and refit the top seal. Use caution when
doing this, as the cut edges of flexible liners may be sharp.
The surfaces of the liner must be physically sound. If gaps or
holes are present, the metal liner must be removed and replaced
(Fix 4). Finally, confirm that the metal liner is the correct size for
the appliances to be installed. Use the GAMA tables and rules.
If a metal liner is not present, a clay tile liner must be present, or
the chimney must be lined (Fix 4).
Use a flashlight and small mirror at the cleanout or vent connector
to inspect the clay tile liner. If any of the following problems are
present:
Tile sections misaligned
Tile sections missing
Gaps between tile sections
Signs of condensate drainage at the cleanout or vent
connectors
Mortar protruding from between tile sections
Use of sewer pipe or drainage pipe rather than an approved
fire clay tile reline the chimney (Fix 4).
Next, measure the size of the liner. It may be possible to do this
from the cleanout. The liner must be at least as large as the
minimum size established by the tables in National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest edition and in the National Standard
of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest
editions and amendments. If the liner is too small or too large,
then the chimney must be relined (Fix 4).
CHECK 6 - DILUTION AIR.
If gas-fired appliances are to be vented into a clay tile liner, a
source of dilution air is required.
Dilution air cannot be obtained through:
Induced draft appliances
Natural draft appliances with vent dampers
Sufficient dilution air can ordinarily be obtained through the draft
hood of a natural draft appliance only if the appliance’s vent
connector does not include a vent damper. If dilution air will not
be available, the chimney must be relined (Fix 4).
CHECK 7 - COMPLETE THE INSTALLATION.
If Checks 1 through 6 have been satisfactory, and the liner is an
acceptable size as determined by the tables in National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition and in the National
Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 -
latest editions and amendments, then the clay tile liner can
probably be used as a vent for the gas appliances. However, the
installer must keep in mind the following factors which may render
the tile liner unsuitable for use as a vent:
Extremely cold weather
Long vent connectors
Masonry chimneys with no air gap between the liner and
the bricks. (In practice, this can be difficult to detect.)
Exterior chimneys (The tables in National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest edition and in the National
Standard of Canada, CAN/CSA B149.1 and CAN/CSA
B149.2 - latest editions and amendments assume interior
chimneys.)
If, in the judgment of the local gas utility, installer, and/or local
codes; one or more of the above factors is likely to present a
problem, the chimney must be relined (Fix 4).
FIX 1 - LINER TERMINATION
Any cap or roof assembly used with a liner must be approved by
the liner manufacturer for such use. The liner and cap/roof
assembly must then terminate above the roof in accordance
with the manufacturer’s instructions.