Greenheck Fan 470658 MSX Ventilation Hood User Manual


 
32
®
Model MSX Make-Up Air
Water Wizard™ — Improper Water Supply
Troubleshooting
1. Adjust the Manual Supply Valve
Adjust the manual supply valve (refer to Start-Up,
Water Wizard™). If the recommended water pressure
does not provide enough water, increase the pressure
until the desired water supply is achieved. If the
recommended water pressure provides too much
water, decrease the water pressure until the desired
water supply is achieved.
2. Enter Program Mode
Press and hold
the Enter key for
three seconds to enter
Program Mode. The
display will read “Pro”
when Program Mode is
active.
3. Adjust the On Time Factor
While in the Program Menu, use the Up and
Down keys to navigate through the menu
options until “ont” is displayed.
With “ont” displayed, press the Enter key to
access the setting.
With the setting displayed, use the Up and Down keys
to adjust the setting as needed.
Increase the factor to increase the water supply or
decrease the factor to decrease the water supply.
Press the Enter key to
save the new On Time
Factor and return to the
Program Menu.
NOTE
If the water supply is too low, the media will
continuously appear dry.
NOTE
If the water supply is too high, the media will be
saturated and excessive water will be draining from
the sump tank.
NOTE
Some water drainage is desired to keep the media
flushed, but it should be minimized to utilize the
Water Wizard™.
CAUTION
Only proceed to Steps 2 and 3 if Step 1 does not
correct the problem.
Program Display
On Time Factor Display
NOTE
Changing the On Time Factor by (1) will change the
water supply by approximately 3%.
IMPORTANT
The enter key must be pressed to save the new On
Time Factor.
4. Exit Program Mode
After 15 seconds of idle time the controller will
automatically exit Program Mode