Greenheck Fan 470658 MSX Ventilation Hood User Manual


 
35
®
Model MSX Make-Up Air
IMPORTANT
Be sure to read and follow the manufacturer’s
recommendations before using any cleaning fluid.
CAUTION
Caution should be used to avoid injury when venting
the coil. High pressure and/or high temperature
fluids can cause serious injuries.
Chilled Water Coils
Test the circulating fluid for sediment, corrosive
products and biological contaminants. Make the
necessary corrective measures.
Maintain adequate fluid velocities and proper filtering
of the fluid.
If automatic air vents are not utilized, periodic venting
of the coil is recommended to remove accumulated air.
Cooling Coils
Inspect the coil for signs of corrosion and/or leaks.
Repair any leaks as required.
Inspect the coil’s surface for foreign material. If the
coil surface needs cleaning, clean the coil from the
leaving air-side so that foreign material will be washed
out of the coil rather than pushed farther in.
Inspect and clean the drain pan to prevent the growth
of algae and other organisms.
Maintenance - Routine
continued
WARNING
Repair and replacement of the coil and the
connecting piping, valves, etc., should be performed
by a qualified individual.