Hobart HQC90 Freezer User Manual


 
– 26 –
Access the Sys Par 2 menu as shown on page 21.
From Sys Par 2, select MODE.
MODE
From Mode Parameters, select CHILL.
(BACK returns to SYS PAR 2.)
CHILL
Set the TARGET Temp using the or keys.
Range: [33°F to 40°F].
Select NEXT to move to the next field.
(BACK returns to the previous field.)
Set the AIR Temp using the or keys.
Range: [10°F to 40°F].
Select NEXT to move to the next field.
Set the HOLD Temp using the or keys.
Range: [10°F to 40°F].
Select NEXT to move to the next field.
Set the HIGH ALARM Temp using the or keys.
Range: [35°F to 60°F].
Select NEXT to move to the next field.
Set the LOW ALARM Temp using the or keys.
Range: [–30°F to 34°F].
Select NEXT to move to the next field.
Set the CHILL MAX Temp using the or keys.
Range: [40°F to 55°F].
(NEXT returns to the TARGET TEMP screen.)
Select ENTER to keep any changes and return to
Mode Parameters.
(CANCEL retains the previous settings and returns to
Mode Parameters.)
MODE PARAMETERS
CHILL FREEZE
SOFT CHILL
BACK
CHILL MODE EDITOR
TARGET 37
°F
BACK NEXT
CANCEL ENTER
CHILL MODE EDITOR
AIR 10
°F
BACK NEXT
CANCEL ENTER
CHILL MODE EDITOR
HOLD 37
°F
BACK NEXT
CANCEL ENTER
CHILL MODE EDITOR
HIGH ALARM 45
°F
BACK NEXT
CANCEL ENTER
CHILL MODE EDITOR
LOW ALARM 32
°F
BACK NEXT
CANCEL ENTER
CHILL MODE EDITOR
CHILL MAX 40
°F
BACK NEXT
CANCEL ENTER
NOTE: To extend the Target Temp range for Chill
and Soft Chill modes, first change the CHILL MAX
value. Then change the Target Temp. The Target
Temp range can be extended to as high as 55°F.
SYS PAR 1 09:07:31
CLOCK TEMPS IN °F
PROBES LOGGING
SETUP MENU MORE
SYS PAR 2 09:08:41
REMOTE ALARM MODE
ALARMS BUZZER
BACK FAC PRESETS