– 27 –
• Access the Sys Par 2 menu as shown on page 21.
• From Sys Par 2, select MODE.
MODE
• From Mode Parameters, select SOFT CHILL.
(BACK returns to SYS PAR 2.)
SOFT CHILL —
Assures against freezing by reducing air flow at end of cycle or by increasing air temp.
[ % ] x Chill Time = Time when reduced air flow occurs.
Range: [10% to 90% ].
• Set the By Time % using the ↓ or ↑ keys.
• Select NEXT to move to the next field.
[_°F ] + Target Temp = Temp when reduced air flow occurs.
Range: [ 5 to 20 °F].
• Set the By Temp degrees using the ↓ or ↑ keys.
• Select NEXT to move to the next field.
(BACK returns to the previous field.)
[ 2nd Temp ] = Sets an alternate Air Temp during the Soft Chill cycle.
Range: [ 10°F to 40°F ]. Normal Air Temp (regular chill cycle) = 10 °F.
• Set the 2nd Temp degrees using the ↓ or ↑ keys.
(NEXT returns to the By Time field.)
• Select ENTER to keep any changes and return to
Mode Parameters.
(CANCEL retains the previous settings and returns to
Mode Parameters.)
MODE PARAMETERS
CHILL FREEZE
SOFT CHILL
BACK
SOFT CHILL EDITOR
↓BY TIME 70%↑
←BACK NEXT→
CANCEL ENTER
SOFT CHILL EDITOR
↓BY TEMP 5
°F↑
←BACK NEXT→
CANCEL ENTER
SOFT CHILL EDITOR
↓2ND TEMP 28
°F↑
←BACK NEXT→
CANCEL ENTER
SYS PAR 1 09:07:31
CLOCK TEMPS IN °F
PROBES LOGGING
SETUP MENU MORE
SYS PAR 2 09:08:41
REMOTE ALARM MODE
ALARMS BUZZER
BACK FAC PRESETS