WATER FLOW REQUIREMENT FOR COPELAND WATER COOLED CONDENSING UNITS *
Gallons per hour per 1,000 BTU/hr (Net)
Temperature Difference, Entering Water to Condensing
20
°F T.D. 30°F T.D.
Operating
Conditions Series Parallel Series Parallel
Water Flow Water Flow Water Flow Water Flow
90°F Condensing
45°F Evap. 8.1 10.1 5.5 6.8
15°F Evap. 8.9 11.1 6.0 7.5
-10°F Evap. 10.0 12.5 6.8 8.5
100°F Condensing
45°F Evap. 8.2 10.3 5.6 6.9
15°F Evap. 9.2 11.5 6.2 7.8
-10°F Evap. 10.4 13.0 7.1 8.8
110°F Condensing
45°F Evap. 8.5 10.5 5.7 7.1
15°F Evap. 9.5 11.8 6.4 8.0
-10°F Evap. 10.9 13.5 7.4 9.2