E. Electrical Connection
WARNING
1. Electrical connection must be hard-wired and must meet national, state, and
local electrical code requirements. Failure to meet these code requirements
could result in death, electric shock, serious injury, re, or extensive damage
to equipment.
2. This unit requires an independent power supply. See the nameplate for proper
voltage and breaker/fuse size. Failure to use a proper breaker or fuse can
result in a tripped breaker, blown fuses, or damage to existing wiring. This
could lead to heat generation or re.
3. THIS UNIT MUST BE GROUNDED. Failure to properly ground this unit could
result in death or serious injury.
4. Electrical connection must be made in accordance with the instructions on
the"WARNING"tag,providedwiththepigtailleadsinthejunctionbox.See
Fig. 3.
•Usuallyanelectricalpermitandservicesofalicensedelectricianarerequired.
•Themaximumallowablevoltagevariationis±10percentofthenameplaterating.
•Thewhiteleadmustbeconnectedtotheneutralconductorofthepowersource.
CAUTION! Miswiring may result in severe damage to the icemaker. See Fig. 3.
•Theopeningforthepowersupplyconnectionis7/8"DIAtota1/2"tradesizeconduit.
Fig. 3
115-120/60/1
WARNING
ELECTRICAL CONNECTION
THIS UNIT MUST BE GROUNDED
Failure to properly ground or wire
this unit could result in death,
serious injury, or severe damage
to the icemaker. The white lead
must be connected to the neutral
conductor of the power source.
See diagram below.
4A4766-010
JUNCTION BOX
1
15-120V
BROWN
WHITE
L
N