Figure 12 - Automatic Gas Valve
Gas Valve Safety Shutdown Test
WARNING
Electrical shock hazard. Follow instructions to turn
off electric power. Failure to do so could result in
death or serious injury.
!
Ignition system safety shutoff device must be tested after
placing boiler in operation.
With main burners ring, disconnect ignition cable from
intermittent pilot control box. Gas valve should shut off
main burners. TURN OFF ELECTRIC POWER to boiler before
reconnecting ignition cable, to prevent electric shock.
Adjust Pilot Burner
1.
Remove screw cover over pilot adjusting screw.
2.
Insert small screwdriver and adjust ame as needed
See
Figure 12 & 13
. Turn screw counterclockwise
to increase ame, clockwise to decrease.
Main Burner(S)
Main burners do not require primary air adjustment and are
not equipped with primary air shutters.
Main burner ames form sharp blue inner cones in softer
blue outer mantel, with no yellow. Puffs of air from blow-
ing on ame or stamping on oor will cause ames to turn
orange momentarily. This is not unusual. Remain still when
observing main burner ames. See
Figure 14, Page 22
.
If ame appearance is not correct, check main burner
ori ces, burner throat and ame ports for dust and lint
obstruction. It may be necessary to remove rollout shield
to observe main burner ames. Replace rollout shield after
observation.
Adjust Limit Controls
Instructions for each control are included with the controls.
Recommended Boiler Water Temperatures
Settings can be changed after you have had some idea how
the system works. Example: If your system does not give
enough heat in very cold weather, you can raise limit setting
to 190°F.
CHECKING AND ADJUSTING
Figure 13 - Pilot Flame Adjustment