Thermador P30 Range User Manual


 
Step 1: Ventilation Requirements
It is strongly recommended that a
suitable exhaust hood be installed
above the range. Downdraft
ventilation should not be used. The
table below indicates the
Thermador hoods, by model
number, that are recommended
for use with all ranges.
1. Select Hood and
Blower Models:
For wall installations, the hood
width must, at a minimum,
equal the width of the range
cooking surface. Where
space permits, a hood larger
in width than the cooking sur-
face may be desirable for im-
proved ventilation perfor-
mance.
For island installations, the
hood width should, at a mini-
mum, overhang the range
cooking surface by 3" on each
side.
2. Hood Placement:
For best smoke elimination,
the lower edge of the hood
should be installed 36" above
the range cooking surface.
(See Fig. 1).
If the hood contains any com-
bustible materials (i.e. a wood
covering), it must be a mini-
mum of 40" above the cooking
surface.
3. Consider Make-Up
Air:
Due to the high volume of ven-
tilation air, a source of outside
replacement air is recom-
mended. This is particularly
important for tightly sealed and
insulated homes.
A qualified heating and venti-
lating contractor should be
consulted.
IMPORTANT:
Ventilation hoods and blowers are
designed for use with single wall
ducting. However, some local
building codes or inspectors may
require double wall ducting. Con-
sult local building codes and/or
local agencies, before starting, to
assure that hood and duct instal-
lation will meet local requirements.
Do not install a microwave oven/
ventilator combination above the
range, as these type of units do
not provide the proper ventilation
and are not suitable for use with
the range.
2
Notes:* For wall installations where adequate space is available, the installer or user may elect to
use a hood that is wider than the rangetop cooking surface. This may be particularly beneficial
for installations having a long duct run or when heavy usage of the grill is anticipated, in which
improved capturing of the cooking exhaust is desired.
** Thermador offers a choice of remote (VTR1030D or VTR1530D) or in-hood (VTN1030C)
blowers for use in wall installations.
*** Hood models PHH30DS and PHH36DS include a 600-CFM built-in blower. For optimal
ventilation, a hood model with 1000-CFM blower or greater is recommended for ranges
having a griddle or grill.
VTR1030D,
VTR1530D,
or VTN1030C
36" RANGE
HNI42YS
HTNI42YS
VTR1030D
or VTR1530D
PH36CS / 42CS
PHE36 / 42
WALL INSTALLATION ISLAND INSTALLATION
RANGE WIDTH
HOOD* BLOWER** HOOD BLOWER
30" RANGE
PH30CS
PHE30 / 36
VTR1030D,
VTR1530D,
or VTN1030C
HNI42YS
HTNI42YS
VTR1030D
or VTR1530D
HNW36YS
VTR1030D,
or VTR1530D
HNW36YS / 42YS
VTR1030D,
or VTR1530D
PHH30DS***
--- N/A ---
PHH36DS***
--- N/A ---