Trane Tracer Unit Ventilator Ventilation Hood User Manual


 
UV-SVP01A-EN 13
Table 2: End Device Specifications
Device Characteristic Description
Fan Status Switch Material Contact Blade—Pilot duty rated
Operating Temperature Range -40°F/250°F (-40°C/120°C)
Contact Form SPST-NO
Preset Fan status - 0.07”
Low Temperature Detection Switch (Freezestat)
Trip Temperature:
36°F ± 2°F
(2°C + - 1.11°C)
Release Temperature
44°F ± 3°F
(6.67°C + - 1.67°C)
Rating—Auto Reset
Pilot Duty
(24 VAC)
120 VAC 240 VAC
FLA 10.0 5.0
LRA 60.0 30.0
OutsideAir Sensor/discharge AirSensor/Entering
Water Temperature Sensor/Unit Mounted, Zone
Return-air Temperature Sensor
Sensing Element
Thermistor 10 KOhms @ 77°F ± 1.8°F (25°C
±1°C)
Standard End Devices