WhisperKool 5000TIR Refrigerator User Manual


 
Page 31
CPSM
Mode
(Cont.)
CCT - Cellar Pre-Chill Duration: This parameter is set to 6 hours, but can be changed between
0-23.5 hours.
Con/Cof – Compressor On time (Con) and O time (Cof) with a Probe 1 failure/Alarm. These
parameters are set at Con 40 min/Cof 10 min. In the event that there is a Probe 1 failure/Alarm,
the compressor/refrigeration system automatically starts a predetermined ON/OFF cycle, which
is controlled by the Con and the Cof parameters. The customer can adjust these parameters to
maintain the desired Bottle temperature.
Alarm Codes
Message Cause Solution
“P1”
Bottle Probe is Unplugged Attach Bottle Probe to Unit
Faulty Bottle Probe Connection 1. Check Bottle Probe attachment at circular connector
2. Check Bottle Probe connection at green terminal block on
back of controller
Defective Bottle Probe Replace the Bottle Probe
“P2” Faulty Evaporator Probe
Connection
Check Evaporator Probe connection at green terminal block on
back of controller
Defective Evaporator Probe Replace the Evaporator Probe
“HA” Defective Bottle Probe Replace the Bottle Probe
“LA” The Bottle Probe is sensing a
temperature of 4° below the set
point
Allow the room to warm up which will increase the temperature
of the wine
Defective Bottle Probe Replace the Bottle Probe
“POF” The keypad is locked Hold “Up” and “Down” buttons for 3 to 5 seconds to disable,
“PON” should appear