Xantrex Technology 815-3024 Microwave Oven User Manual


 
97-0019-01-01 53
Configuring the Freedom SW using the SCP
Custom Battery Settings Menu
The Custom Battery Settings menu can be viewed if Custom is
selected as the Batt Type. This menu allows you to adjust charging
and equalization voltage for batteries with specifications that fall
outside the default settings for the battery types the Freedom SW
offers. You can also adjust the temperature compensation constant
for the battery temperature sensor on this menu.
EQUIPMENT DAMAGE
Consult your battery manufacturer and associated documentation before
setting a custom battery type to avoid damaging your batteries during
charging or equalization.
Failure to follow these instructions can damage the unit and/or
damage other equipment.
Figure 29 Custom Settings Menu Screen
FSW3012 00: Cust Settings
Eqiz Support
Eqiz Voltage
Bulk Voltage
Absorb Voltage
Float Voltage
BattTempComp
[Enabled]
[16.0V]
[14.4V]
[14.4V]
[13.5V]
[-27mV/K]
Appears only when
Equalize support is Enabled.
Follow procedures on “To select and change a
configurable setting:” on page 38 to change the settings.
Table 12 Setting Defaults and Ranges
Model Freedom SW 2012 / 3012 Freedom SW 2024 / 3024
Item Default Min Max Default Min Max
Eqlz Support Enabled Enabled,
Disabled
Enabled Enabled,
Disabled
Eqlz Voltage 15.5V 13.5V 16.0V 31.0V 27.0V 32.0V
Bulk Voltage 14.4V 12.0V 16.0V 28.8V 24.0V 32.0V
Absorb Voltage 14.4V 12.0V 16.0V 28.8V 24.0V 32.0V
Float Voltage 13.5V 11.0V 16.0V 27.0V 22.0V 32.0V
Batt Temp Comp 27-mV 0-mV 45-mV 54-mV 0-mV 90-mV
IMPORTANT:
All settings for configuring a custom battery type are
based on the default settings for a flooded battery type.
Freedom SW 3K2K InvChg Owners Guide.book Page 53 Thursday, July 31, 2014 1:42 PM