Fig.5-3: Series connection for positive/negative output voltages
(*) Diodes are user supplied.
3. Programming by external resistor:
Programming by external resistor is possible. Refer to
4. Programming via the Serial
nication port is referenced to the IF_COM
Communication port (RS232/RS485):
which is isolated from the power supply output potential.
Therefore power supplies connected in series can be
to Chapter 7 for details.
5.14.2 Series connection for positive and negative output voltage
In this mode, two units are confi
ured as a positive and negative output. Set the Output Current limit
of each power supply to the max
mum that the load can handl
e without damage. It is recommended
that diodes be connected in parallel with each unit output to prevent reverse voltage during start
in case one of the units shuts down. Each diode should be rated to at least the power supply rated
nd output current. Refer to Fig.5
3 for this operating mode.
Remote programming in series operation for positive and negative output voltage
1. Programming by external voltage:
The analog programming circuits of this power su
enced to the negative output potential.
Therefore, the circuits used to control each series
connected unit must be separated and floated from
2. Using the SO function and PS_OK signal:
Off and PS_OK circuits are referenced to
ated interface common, IF_COM (J1
The IF_COM terminals of the units can be co
nected to obtain a single control circuit for the power
supplies connected in series.
3. Programming by external resistor:
Programming by external resistor is possible. Re
to section 6.5 for details.
4. Programming via the Serial
Communication port (RS232/RS485):
The communication port is referenced to the
IF_COM which is isolated from the power supply
output potential. Therefore power supplies co
can be chained using the Remote
Out connectors. Refer to chapter 7