5-6 l Maintenance
Cleaning the Brazed Plate Evaporator
(continued)
5 Remove RTD from bottom of evaporator.
6 Connect 3/8-inch tubing to the 3/8-inch connections of the heat exchanger.
SEE below to install customer-supplied chemical pump and solution fitted to the
heat exchanger.
7 Back-flush the solution through the heat exchanger and the chiller.
8 Flush the heat exchanger and the chiller piping with fresh water after
cleaning.
9 Reconnect the chiller pump to the heat exchanger. Remove the cap in the heat
exchanger and reconnect the hose to the pump.
NOTE: These connections
may vary depending on the
model you have purchased.
Be sure to see the labeling on
your particular unit.
Acid
solution
Fluid circuit
Heat
Exchanger
To pump
To Process
connection
Valve
Pump
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when working on the chiller,
especially when working on or around the compressor and condenser. These
devices can reach over 160°F {71°C}. Allow these devices to cool before
performing any maintenance or troubleshooting.