Conair UGH031-0209 Refrigerator User Manual


 
Appendix l I-1
Control Setup
1/32 DIN Watlow SD controller Setup Sheet
Enter the following parameters
Menu Parameter Description Setting
Set Up Page Sen Input sensor type RTD
up & down for C-F Temperature Units (degrees) F
3 seconds S.dec Temperature Decimal Places 0
IS.en Infosense no
SP.Lo Set Point Low Limit 40.0
SP.hi Set Poing High Limit 65
Ftr.e Input Filter Both
Flt.r Filter value - Seconds 5
Ot1 Output 1 function heat
Ctr1 Control Method 1 ftb
Ftb1 Cycle time 1 10
PL 1 Power Limit 1 100%
PSL1 Output Power Limit Sacle Low 1 0%
PSH1 Output Power Limit Sacle High 1 90%
nLF1 Output Non-Linear Function 1 Off
Ot2 Output 2 Function - SP devaition dE.AL
hys2 Alarm Hysteresis 2 1.5F
Lgc2 Alarm relay state on alarm - open Al o
Lat2 Alarm 2 latching nLat
dSP2 Alarm 2 Message on
ACLF AC line frequency 60
Unit Units of Measurement SI
I.Err Input error latching nLat
FAIL Input Error Failure Mode bPLS
Man Manual Error Level 0%
dSP Active Displays nor
rP Ramping Mode off
LOC Security Lockout 3
Programming Adv and INF keys 6 seconds
P1 Temperature Units - C-F F
P2 Low Temp Dev. alarm - A2.Lo -4
P3 High Temp dev Alarm - A2.HI 20
P4 Proportional Band Hot Gas - pb.ht 3
P5 Intergral Hot Gas - It.ht 3.4
P6 Derivative - dE.ht 0.1