Fluke 1625 Kitchen Utensil User Manual


 
1625
Users Manual
18
Minimal current in single
branch to be measured:
0.5 mA with transformer (1000:1)
0.1 mA with transformer (200:1)
Max. interference current
through transformer:
3 A with a transformer (1000:1)
Resistance Measurement (R~)
Measuring method: current and voltage measurement
Measuring voltage: 20 V AC, square pulse
Short circuit current: > 250 mA AC
Measuring frequency: 94, 105, 111, 128 Hz selected manually or auto-
matically (AFC)
Measuring
Range
Display Range Resolution
Intrinsic
Error
Operating
Errors
0.001 ... 2.999 0.001
3.0 ... 29.99 0.01
0.020 ... 30 ... 299.9 0.1
300 k 300 ... 2999 1
± ( 2 %
of m.v.
+2 digit )
± ( 5% of m.v.
+5 digit )
3.0 k ... 29.99 k 10
30.0 k ... 299.9 k 100
Measuring time: typ. 6 sec.
Max. interference voltage: 24 V, with higher voltages measurement will not
be started
Max overload: Urms max. = 250 V