Stakeless Earth/Ground Resistance Testing
Principle of Operation
69
>10 cm
Erder
edw064.eps
Pushing the START-button will display the value of R
E
.
Note
In this particular mode the values of RH and RS have no meaning.
Settings on the Tester
Refer to the Operation section in the Testers instruction manual.
The rotary switch of the tester must be in the R
E
3 pole position.
- U
m
Set Test Voltage to 48 V (standard value)
- R
k
Set compensation resistance to 0,000 Ohms
- I Set transformer ratio to 1000 (standard value)
- R* Set to OFF (no meaning in this mode).