Fluke 1625 Kitchen Utensil User Manual


 
Stakeless Earth/Ground Resistance Testing
Principle of Operation
67
If the parallel connection of resistors, R1...Rn is considerably lower than the
ground connection under test R
X
:
R
RRR
X
n
<<
++
111
1
21
then
I
U
R
X
= is a reasonable approximation.
The test voltage (U) is applied without disconnecting ground rod and/or the
direct electrical connection by means of a clamp-on current transformer and
the current detected by a second current transformer.
R
X
R
1
R
2
R
n-1
R
n
Current
I
Voltage
U
edw062.eps
After synchronous rectification of current and voltage the tester displays R
X
.