02/04 4034-102 Rev F 19
HRV200PLUS INSTALLATION INSTRUCTIONS
Dimension Descriptions
A Clearance above the ground, a veranda, porch, deck or balcony - 12 inches (30 cm) minimum. *
B Clearance to window or door that may be opened 10,000 BTUs or less, 6 inches (15 cm) minimum; 10,000-50,000 BTUs, 9 inches (23 cm)
minimum; over 50,000 BTUs, 12 inches (30 cm) minimum. *
C Clearance to permanently closed window 12inches (30 cm) minimum - recommended to prevent condensation on window.
D Vertical clearance to ventilated soffit located above the termination within a horizontal distance of 2 feet (60 cm) from the centerline of the
termination 18inches (46 cm) minimum. **
E Vertical clearance to unventilated soffit - 12 inches (30 cm) minimum. **
F Clearance to outside corner - 6 inches (15 cm) minimum.
G Clearance to inside corner - 6 inches (15 cm) minimum.
H Not to be installed above a meter/regulator assembly within 3 feet (90 cm) horizontally* from the center line of the regulator (Canada only)
I Clearance to service regulator vent outlet 3 feet (.91 m) U.S. minimum and 6 feet (1.8 m) Canada minimum. *
J Clearance to non-mechanical air supply inlet into building or the combustion air inlet to any other appliance 9 (23 cm) U.S. minimum and 12
inches (30 cm) Canada minimum. *
K Clearance to mechanical air supply inlet - 3 feet (.91 m) U.S. minimum and 6 feet (1.8 m) Canada minimum. *
L Clearance above a paved sidewalk or paved driveway located on public property - 7 feet (2.1m) minimum.
A vent may not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both
dwellings.
M Clearance under veranda, porch, deck or balcony - 12 inches (30 cm) minimum. * Recommended 30 inches (76 cm) for vinyl or plastic.
Only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor. *
N Vertical clearance between two horizontal termination caps 12 inches (30 cm) minimum.
O Horizontal clearance between two horizontal termination caps 12 inches (30 cm) minimum.
P 6 - Non-vinyl sidewalls
12 Vinyl sidewalls
Q 18 Non-vinyl soffit and overhang
42 Vinyl soffit and overhang
R 8 ft.
U 6 min. Clearance from sides of electrical service.
W 12 min. Clearance above electrical service.
* As specified in CGA B149 Installation Codes
Note: Local codes or regulations may require different clearances.
** Clearance required to vinyl soffit material 30inches (76 cm) minimum.
Note: Location of the vent termination must not interfere with access to the electrical service.
WARNING!
In the U.S.: Vent system termination is NOT permitted in screened porches. You must follow side wall, overhang and ground clearances as stated
in the instructions.
In Canada: Vent system termination is NOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more
sides open. You must follow all side wall, overhang and ground clearances as stated in the instructions.
Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet
these requirements.