Heat Controller A-13 Refrigerator User Manual


 
17
NOTES:
1. Wire size based on 60°C rated wire insulation and 30°C Ambient Temp. (86°F).
2. For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the
ampacity of each conductor.
When installed, the unit must be electrically grounded in accordance with local
codes or, in the absence of local codes, with the National Electrical Code,
ANSI/NFPA 70, if an external electrical source is utilized.
IMPORTANT: THIS UNIT IS AP PROVED FOR USE WITH COPPER CONDUCTORS
ONLY
CONNECTED TO UNIT CONTACTOR.
WARRANTY MAY BE JEOPARDIZED IF ALUMINUM WIRE IS CONNECTED TO
UNIT CONTACTOR.
Special instructions apply for power wiring with aluminum conductors: Warranty
is void if connections are not made per instructions.
Attach a length (6؆ or more) of recommended size copper wire to the unit contactor ter-
minals L1 and L3 for single phase, L1, L2 and L3 for three phase.
Select the equivalent aluminum wire size from the tabulation below:
Splice copper wire pigtails to aluminum wire with U.L. recognized connectors for copper-
aluminum splices. Please exercise the following instructions very carefully to obtain a
positive and lasting connection:
1. Strip insulation from aluminum conductor.
2. Coat the stripped end of the aluminum wire with the recommended inhibitor, and
wire brush the aluminum surface through inhibitor. INHIBITORS: Brundy-Pentex “A”;
Alcoa-No. 2EJC; T & B-KPOR Shield.
3. Clean and recoat aluminum conductor with inhibitor.
4. Make the splice using the above listed wire nuts or split bolt connectors.
5. Coat the entire connection with inhibitor and wrap with electrical insulating tape.
FIGURE 17
RECOMMENDED BRANCH CIRCUIT DISCONNECT LOCATION
TO POWER
TO THERMOSTAT
BRANCH
CIRCUIT
DISCONNECT
I317A
AWG Copper AWG Aluminum Connector Type and Size
Wire Size Wire Size (or equivalent)
#12 #10 T & B Wire Nut PT2
#10 # 8 T & B Wire Nut PT3
# 8 # 6 Sherman Split Bolt TSP6
# 6 # 4 Sherman Split Bolt TSP4
# 4 # 2 Sherman Split Bolt TSP2
TABLE 5
200 64443322
150 86644433
100 10 8866644
50 14 12 10 10 8866
15 20 25 30 35 40 45 50
BRANCH CIRCUIT AMPACITY
SUPPLY WIRE
LENGTH-FEET
*Taken from National Electric Code
TABLE 4
BRANCH CIRCUIT COPPER WIRE SIZE
(Based on 1% Voltage Drop)*