4 TON - 13 SEER MODELS
RPM WATTS
775 470
800 525
830 595
RPM WATTS
1015 505
1030 545
1050 600
1075 640
1095 680
1120 735
1150 800
1175 870
1200 950
RPM WATTS
1320 705
1335 775
1345 825
1355 855
1370 935
1385 1000
CAPACITY: 4 TON - 13 SEER
VOLTAGE: 208/230 - 460
EXTERNAL STATIC PRESSURE
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.10 1.20 1.30 1.40 1.50
1200
1300
1400
1500
1600
1700
1800
1900
2000
RPM WATTS
775 425
795 470
820 515
855 560
885 640
RPM WATTS
780 360
805 390
825 425
850 475
870 495
900 540
930 600
955 650
970 710
RPM WATTS
835 390
855 410
870 445
900 490
920 530
940 560
960 625
995 700
1020 790
RPM WATTS
885 410
910 450
925 480
940 515
960 580
980 605
1010 680
1035 755
1065 840
RPM WATTS
935 440
950 470
960 510
980 550
1005 605
1025 655
1050 740
1075 800
1115 860
RPM WATTS
975 475
990 510
1010 550
1025 600
1050 660
1075 715
1100 760
1130 840
1180 900
RPM WATTS
1070 550
1085 590
1105 615
1125 670
1145 710
1165 770
1190 840
1220 920
1240 1010
“M”
RPM WATTS
1120 570
1135 610
1155 650
1175 700
1195 755
1215 810
1235 890
1260 955
1295 1060
RPM WATTS
1170 600
1185 640
1200 700
1220 745
1235 800
1270 870
1280 930
1305 1010
1330 1105
RPM WATTS
1220 635
1235 685
1245 730
1270 780
1285 845
1305 915
1330 985
1350 1070
1375 1160
RPM WATTS
1265 655
1285 730
1300 770
1315 825
1330 890
1350 940
1365 1020
1385 1115
“N”
AIR
FLOW
CFM
DRIVE PACKAGE “L” “M”
MOTOR H.P. 1/2 3/4
BLOWER SHEAVE 6.4؆ PITCH DIAMETER 5.7؆ PITCH DIAMETER
MOTOR SHEAVE 2.8؆ - 3.8؆ PITCH DIAMETER 3.4؆ - 4.4؆ PITCH DIAMETER
TURNS OPEN 0 1 2 3 4 5 6 0 1 2 3 4 5 6
RPM 1060 1000 955 910 865 825 770 1385 1330 1280 1225 1175 1120 1060
STANDARD INDOOR AIRFLOW - CFM
COMPONENT 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
RESISTANCE - INCHES WATER
WET COIL .035 .040 .060 .070 .085 .100 .110 .120 .125 .130
DOWNFLOW .055 .060 .066 .072 .080 .086 .093 .100 .107 .115
ECONOMIZER
R. A. DAMPER
.05 .06 .07 .08 .09 .10 .11 .12 .13 .15
COMPONENT AIR RESISTANCE
NOTES:
1. PERFORMANCE SHOWN WITH DRY COIL & STANDARD 1؆ FILTERS
2. STANDARD CFM @ .075 LBS./CU. FT.
3. MOTOR EFFICIENCY = 80%
4. BHP = WATTS X MOTOR EFF.
746
5. ADD COMPONENT RESISTANCE TO DUCT STATIC TO DETERMINE TOTAL E.S.P.
RPM WATTS
770 385
790 425
815 455
850 505
875 555
910 610
940 670
“L”
INDOOR AIRFLOW PERFORMANCE FOR 3-5 TON PACKAGE GAS ELECTRIC UNITS – TGC
BELT DRIVE
NOTE: Bold lines separate L, M and N drives respectively.
NOTE: Factory sheave settings are shown in bold print.