– 17 –
EXHAUST CONNECTION
Moist air escapes from each end of the conveyor type dishwasher. The recommended
exhaust requirement is 200 CFM (CLe and CLeR) at the entrance end of the dishwasher
and400CFM(CLe)/175CFM(CLeR)atthedischargeend.Sufcientmake-up
airmustbeprovidedsotheexhaustowresultsinapositivebuildingpressurein
the room in which the unit is located (more outside air than exhaust air). Hoods are
provided with 4" x 16" vent connectors with vent dampers which allow adjustment
during installation. Typical construction is for 'Pant-Leg' hood connections to the
4"x16"ventconnectors(Fig.25and25A).Ventstacksmustbewatertightandt
inside the vent connector openings.
CLe-Series
Fig. 25
4" X 16"
VENT
CONNECTOR
PA NT-LEG DUCT
ENTRANCE
VENT STACK
DAMPER
EXIT
VENT STACK
DAMPER
INTERNAL VENT
SHOULD REMAIN
OPEN UNLESS
AIRFLOW ADJUSTMENT
IS NECESSARY
DEFLECTOR PAN