2.5 ELECTRICALCONNECTIONS
It is advised that this appliance be connected to a power supply that is controlled by the ventilation system.
This will prevent the appliance from being operated without the ventilation hood on.
If your appliance is single phase, it requires a hardwired, flexible conduit electrical connection, using
conductors size appropriately for the power requirements listed below. Hardwired units require installation
of a restraint device mounted to substantial building structure.
ELECTRICAL
REQUIREMENTS
Model KW/Hr
200
2
208 220 230 240 480
200
2
208 220 230 240 480 346/200V 380/220V 400/230V 415/240V
SELV14X 14 65 67 65 61 58 29 37 39 37 35 34 17 23 21 20 20
SELV14TX
(both tanks)
14 65 67 65 61 58 29 37 39 37 35 34 17 23 21 20 20
SELV14 17 798278747136464845434121 28 26 25 24
SELV14T
(both tanks)
17 79 82 78 74 71 36 46 48 45 43 41 21 28 26 25 24
Single Phase (2 wire + ground) 3 Phase (3 wire + ground) 3 Phase "Y" (4 wire + ground)
Nominal Amps Per Line (50/60 HZ)
1. Each fryer requires it's own separate power supply connection. 2. 200V Units will operate at 92% of rated power. 3. Power supply for Basket Lifts
and Filter motor is wired into the fryer's high voltage line terminal block, except for 480V. 480VAC line voltage requires a separate single phase
service for the filter motor and Basket Lifts( If equipped) rated for 115V,8.0A for North America and 220-240V,4.0A for Export to be installed.
CAUTION
Connecting the appliance to the wrong power supply may damage the appliance and void the warranty
WARNING
This appliance must be connected to a power supply having the same voltage and phase as specified
on the data plate located on the inside of the appliance door. DO NOT attempt to connect the appliance
to an electrical supply other than that indicated on the data plate. Electrical connection should be
performed by a qualified electrician
WARNING
The electrical connection used by this appliance must comply with local codes. If there are no local
codes that apply, refer to the National Electrical Code (NEC), ANSI/NFPA 70 for installation in the US.
In Canada, refer to CSA Standard C22.2 and local codes. In all other cases, refer to local and national
codes and regulations.
The appliance must be grounded in accordance with local code, comply with the NEW and ANSI/NFPA
No. 70 latest edition (for US and Canadian installations). In all other cases, refer To local and national
codes and regulations. To comply with European requirements, European models are equipped with
an equalization-bonding clamp. An equalization bonding lead must be connected to this clamp to
provide sufficient protection against potential difference. This clamp, located on the rear of the
appliance is marked with the following universal symbol.
WARNING
A country approved all pole circuit breaker with a minimum open contact gap of 3mm must be used for
proper installation. (CE countries)
WARNING
This equipment must be installed so that the plug (if used) is accessible unless other means for
disconnection from the power supply (e.g: circuit breaker) is provided.
WARNING
If this appliance is permanently connected to fixed wiring, it must be connected by means of copper
wires having a temperature rating of not less than 167°F (75°C), and have a local means of
disconnection from all poles from the mains included in the fixed wiring in accordance with local codes.
WARNING
All power connection wiring for this appliance must be made in accordance with the wiring diagrams(s)
located on the appliance.
CAUTION
Leakage current of this appliance may exceed 10 mA. When permanently connected, a high integrity
protective system employing an RCD rated at 30 mA must be used with this appliance.