Trane RTAA Refrigerator User Manual


 
27
RLC-PRC016-EN
Table P-12 50 Hz RTAA 125 Performance Data English
Entering Condenser Air Temperature (Degrees F)
LWT 75 85 95 105 115
(Deg. F) Tons kW EER Tons kW EER Tons kW EER Tons kW EER Tons kW EER
40 108.8 93.9 13.0 103.2 101.2 11.5 97.3 109.7 10.1 91.0 119.4 8.7 84.4 130.5 7.4
42 112.5 95.6 13.2 106.7 102.8 11.7 100.6 111.3 10.3 94.1 121.1 8.9 87.3 132.2 7.6
44 116.2 97.3 13.4 110.3 104.5 11.9 104.0 113.0 10.5 97.3 122.7 9.1 90.3 133.8 7.7
46 120.0 99.1 13.6 113.9 106.2 12.1 107.4 114.7 10.6 100.5 124.5 9.2 93.4 135.6 7.9
48 123.9 100.9 13.8 117.6 108.0 12.3 110.9 116.5 10.8 103.8 126.2 9.4 95.8 136.5 8.1
50 127.9 102.8 14.0 121.4 109.9 12.5 114.4 118.3 11.0 107.1 128.0 9.6 96.5 135.1 8.2
55 138.1 107.7 14.5 131.0 114.7 13.0 123.5 123.0 11.5 115.6 132.6 10.0 97.7 129.8 8.6
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.00010.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kW input is for compressors only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 10°F.
6. 115°F performance data reflects Adaptive Control Microprocessor control algorithms.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
Performance Data
Table P-11 50 Hz RTAA 110 Performance Data English
Entering Condenser Air Temperature (Degrees F)
LWT 75 85 95 105 115
(Deg. F) Tons kW EER Tons kW EER Tons kW EER Tons kW EER Tons kW EER
40 98.4 85.3 12.8 93.5 92.0 11.4 88.2 99.9 10.0 82.6 108.9 8.6 76.7 119.1 7.3
42 101.7 86.8 13.1 96.7 93.5 11.6 91.2 101.3 10.2 85.5 110.3 8.8 79.4 120.6 7.5
44 105.1 88.3 13.3 99.9 95.0 11.8 94.3 102.8 10.4 88.3 111.8 9.0 82.1 122.1 7.7
46 108.5 89.9 13.5 103.1 96.5 12.0 97.4 104.3 10.6 91.3 113.3 9.2 84.9 123.6 7.8
48 112.1 91.5 13.7 106.5 98.1 12.2 100.5 105.9 10.7 94.3 114.9 9.3 87.7 125.2 8.0
50 115.6 93.2 13.9 109.9 99.7 12.4 103.8 107.5 10.9 97.3 116.5 9.5 90.5 126.7 8.2
55 124.8 97.5 14.4 118.6 103.9 12.9 112.0 111.6 11.4 105.0 120.5 9.9 92.3 123.5 8.5
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.00010.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kW input is for compressors only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 10°F.
6. 115°F performance data reflects Adaptive Control Microprocessor control algorithms.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
Metric
Entering Condenser Air Temperature (Degrees C)
LWT 30 35 40 45
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 342.5 94.8 3.4 324.9 101.9 3.0 306.6 110.0 2.6 287.3 119.0 2.3
8 362.9 97.5 3.5 344.6 104.6 3.1 325.2 112.7 2.7 304.8 121.8 2.4
10 384.3 100.4 3.6 365.0 107.5 3.2 344.6 115.5 2.8 323.1 124.6 2.5
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/kWi). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5.6°C.
6. 115°F performance data reflects Adaptive Control Microprocessor control algorithms.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.
Metric
Entering Condenser Air Temperature (Degrees C)
LWT 30 35 40 45
(Deg. C) kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
6 378.3 104.3 3.4 358.6 112.0 3.0 337.9 120.7 2.7 316.1 130.5 2.3
8 400.8 107.4 3.5 380.1 115.0 3.1 358.3 123.8 2.8 335.4 133.6 2.4
10 424.4 110.7 3.6 402.6 118.3 3.2 379.4 127.0 2.9 355.5 136.7 2.5
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/kWi). Power inputs include compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5.6°C.
6. 115°F performance data reflects Adaptive Control Microprocessor control algorithms.
7. Interpolation between points is permissible. Extrapolation is not permitted.
8. Rated in accordance with ARI Standard 550/590-98.