Trane RTAA Refrigerator User Manual


 
RLC-PRC016-EN30
Jobsite
Connections
Table J-1 Customer Wire Selection
Wire Selection Size Wire Selection Size Wire Selection Size
to Main Terminal Block to Disconnect (1) to Circuit Breaker (1)
Connector Connector Factory Mounted Internal Connector
Unit Rated Terminal Size Wire Range Disconnect Size Wire Range Circuit Breaker Size (3) Wire Range
Size Voltage Ckt 1 Ckt 1 Ckt 1 Ckt 1 Ckt 1 Ckt 1
RTAA 70 200/60 760 Amp Lug Size D 400 Amp Lug Size B 350 Amp Lug Size B
230/60 760 Amp Lug Size D 400 Amp Lug Size B 300 Amp Lug Size B
380/60 335 Amp Lug Size E 250 Amp Lug Size A 200 Amp Lug Size A
460/60 335 Amp Lug Size E 250 Amp Lug Size A 150 Amp Lug Size A
575/60 335 Amp Lug Size E 250 Amp Lug Size A 125 Amp Lug Size A
380/50 335 Amp Lug Size E 250 Amp Lug Size A 150 Amp Lug Size A
400/50 335 Amp Lug Size E 250 Amp Lug Size A 150 Amp Lug Size A
415/50 335 Amp Lug Size E 250 Amp Lug Size A 150 Amp Lug Size A
RTAA 80 200/60 760 Amp Lug Size D 400 Amp Lug Size B 400 Amp Lug Size B
230/60 760 Amp Lug Size D 400 Amp Lug Size B 350 Amp Lug Size B
380/60 335 Amp Lug Size E 250 Amp Lug Size A 225 Amp Lug Size A
460/60 335 Amp Lug Size E 250 Amp Lug Size A 175 Amp Lug Size A
575/60 335 Amp Lug Size E 250 Amp Lug Size A 150 Amp Lug Size A
380/50 335 Amp Lug Size E 250 Amp Lug Size A 175 Amp Lug Size A
400/50 335 Amp Lug Size E 250 Amp Lug Size A 175 Amp Lug Size A
415/50 335 Amp Lug Size E 250 Amp Lug Size A 175 Amp Lug Size A
RTAA 90 200/60 760 Amp Lug Size D 600 Amp Lug Size C 500 Amp Lug Size C
230/60 760 Amp Lug Size D 400 Amp Lug Size B 450 Amp Lug Size C
380/60 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
460/60 335 Amp Lug Size E 250 Amp Lug Size A 225 Amp Lug Size A
575/60 335 Amp Lug Size E 250 Amp Lug Size A 175 Amp Lug Size A
380/50 335 Amp Lug Size E 250 Amp Lug Size A 225 Amp Lug Size A
400/50 335 Amp Lug Size E 250 Amp Lug Size A 225 Amp Lug Size A
415/50 335 Amp Lug Size E 250 Amp Lug Size A 225 Amp Lug Size A
RTAA 100 200/60 760 Amp Lug Size D 600 Amp Lug Size C 600 Amp Lug Size C
230/60 760 Amp Lug Size D 600 Amp Lug Size C 500 Amp Lug Size C
380/60 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
460/60 335 Amp Lug Size E 250 Amp Lug Size A 250 Amp Lug Size A
575/60 335 Amp Lug Size E 250 Amp Lug Size A 200 Amp Lug Size A
380/50 335 Amp Lug Size E 250 Amp Lug Size A 250 Amp Lug Size A
400/50 335 Amp Lug Size E 250 Amp Lug Size A 250 Amp Lug Size A
415/50 335 Amp Lug Size E 250 Amp Lug Size A 250 Amp Lug Size A
RTAA 110 200/60 760 Amp Lug Size D 600 Amp Lug Size C 600 Amp Lug Size C
230/60 760 Amp Lug Size D 600 Amp Lug Size C 600 Amp Lug Size C
380/60 335 Amp Lug Size E 400 Amp Lug Size B 350 Amp Lug Size B
460/60 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
575/60 335 Amp Lug Size E 250 Amp Lug Size A 225 Amp Lug Size A
380/50 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
400/50 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
415/50 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
RTAA 125 200/60 760 Amp Lug Size D 600 Amp Lug Size C N/A N/A
230/60 760 Amp Lug Size D 600 Amp Lug Size C 600 Amp Lug Size C
380/60 335 Amp Lug Size E 400 Amp Lug Size B 350 Amp Lug Size B
460/60 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
575/60 335 Amp Lug Size E 250 Amp Lug Size A 225 Amp Lug Size A
380/50 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
400/50 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
415/50 335 Amp Lug Size E 400 Amp Lug Size B 300 Amp Lug Size B
Lug Size A = #4 to 350 MCM per phase
Lug Size B = 2/0 to 250 MCM & 2/0 to 500 MCM per phase
Lug Size C = (2) 400 MCM to 500 MCM per phase
Lug Size D = (2) #4 to 500 MCM per phase
Lug Size E = #6 to 400 MCM per phase
Lug Size F = (2) #2 to 600 MCM per phase
Lug Size G = (2) #1 to 500 MCM per phase
Lug Size H = (4) #2 to 600 MCM per phase
Notes
1. Non-fused unit disconnect and circuit breaker are optional.
2. Copper wire only, sized per N.E.C., based on nameplate minimum circuit ampacity (MCA).
3. Circuit Breaker sizes are for factory mounted only. Field installed circuit breakers need to be sized using HACR breaker recommendations from Table E-1.