VIII. c - G-SERIES PARAMETER SETTINGS (MIT II Control Version):
Control Freezer Models Refrigerator Models
Parameter GF1 GF2 GF3 GF4 GR1 GR2 GR3
ADR* 2 2 2 2 2 2 2
BAU* 9.6 9.6 9.6 9.6 9.6 9.6 9.6
NAF* ON ON ON ON ON ON ON
SPH -5.2 0.1 0.1 32 38.1 39.2 39.2
SPL -10 -4 -4 26.1 34 37 37
SHL -8 -3.1 -3.1 30.2 36 39.2 39.2
SHH -5.2 0.1 0.1 34 40 40 40
SLL -13 -6.2 -6.2 26.1 32 34 34
SLH -10 -4 -4 28 34 37 37
RO 0 000 000
HI 0.1 5 5 35.2 41 41 41
LO -18.4 -10 -10 20 30.2 30.2 30.2
SCL F FFF FFF
HAD n/a n/a n/a n/a n/a n/a n/a
LAD n/a n/a n/a n/a n/a n/a n/a
AC 3 333 333
DEF ELE ELE ELE ELE OFF ELE OFF
IBD 4.0 4.0 4.0 4.0 1.0 2.0 1.0
DDC 20 20 20 20 10 20 10
CDE 75 75 75 75 45.1 70 45.1
DDE 2 222 222
BDD 1 111 000
BSD 32 32 32 32 32 32 32
ODD 10 10 10 10 10 10 10
SD
Starts a new defrost cycle at any time or stops a current defrost cycle.
CFA n/a n/a n/a n/a n/a n/a n/a
CCR n/a n/a n/a n/a n/a n/a n/a
CDL n/a n/a n/a n/a n/a n/a n/a
DOA n/a n/a n/a n/a n/a n/a n/a
DAD n/a n/a n/a n/a n/a n/a n/a
APD n/a n/a n/a n/a n/a n/a n/a
ATD n/a n/a n/a n/a n/a n/a n/a
AAS n/a n/a n/a n/a n/a n/a n/a
CL Set the hours and minutes in military time.
DAY Set the year, month, day of the month and day of the week.
DS ON ON ON ON ON ON ON
DL1 OFF OFF OFF OFF OFF OFF OFF
DL2 OFF
11:30am
OFF OFF OFF OFF OFF
DL3 OFF
5:30pm
OFF OFF OFF OFF OFF
DL4 OFF OFF OFF OFF OFF OFF OFF
DCF n/a n/a n/a n/a n/a n/a n/a
CON 19 19 19 19 11 11 11
COF 7 7 7 7 10 10 10
EL
Will display evaporator coil temp in real time every time an arrow is pressed.
DL
Will display discharge line temp in real time every time an arrow is pressed.
CB
Will display cabinet air temp in real time every time an arrow is pressed.
PLn*
Will display power line voltage in real time every time an arrow is pressed.
RCO*
Turns ON/OFF the compressor relay for 10-seconds or until an arrow is pressed.
RdF*
Turns ON/OFF the defrost relay for 10-seconds or until an arrow is pressed.
RFA*
Turns ON/OFF the blower relay for 10-seconds or until an arrow is pressed.
RDH*
Turns ON/OFF the door heater triac for 10-seconds or until an arrow is pressed.
PRO* Set the controller in receiving mode for programming.
CEP* Clear all controller memories and reloads the factory default parameters.
REF*
Firmware revision in the format X9.9 (X=version, 9=major revision, 9=minor revision).
VIII. CONTROL PARAMETERS
*MIT II control version only.