VIII. CONTROL PARAMETERS
VIII. e - R-SERIES PARAMETER SETTINGS (MIT II Control Version):
Control Freezer Models
Parameter RF1 RF2 RF3 RF4 RF5
ADR 2 2222
BAU 9.6 9.6 9.6 9.6 9.6
NAF ON ON ON ON ON
SPH -15.4 -10 0.1 0.1 -5.2
SPL -20.2 -15.4 -4 -4 -10
SHL -15.4 -13.6 -2.2 -2.2 -8
SHH -10 -10 0.1 0.1 -5.2
SLL -20.2 -20.2 -6.2 -6.2 -13
SLH -17 -15.4 -4 -4 -10
RO 0 0000
HI 5.2 5.2 5 5 0.1
LO -25.6 -25.6 -10 -10 -17.8
SCL F FFFF
HAD 15 15 15 15 15
LAD 2 2222
AC 3 3333
DEF ELE ELE ELE ELE ELE
IBD 4.0 4.0 4.0 4.0 4.0
DDC 30 20 20 20 20
CDE 55 75 75 70 70
DDE 5 2222
BDD 1 1111
BSD -10 32 32 32 32
ODD 10 10 10 10 10
SD
Starts a new defrost cycle at any time or stops a current defrost cycle.
CFA ON OFF OFF ON ON
CCR 20 20 20 20 20
CDL 220.1 220.1 220.1 220.1 220.1
DOA ON ON ON ON ON
DAD 15 15 15 15 15
APD 2 2222
ATD 10 10 101010
AAS OFF OFF OFF OFF OFF
CL Set the hours and minutes in military time.
DAY Set the year, month, day of the month and day of the week.
DS ON ON ON ON ON
DL1 OFF OFF OFF OFF OFF
DL2 OFF OFF OFF OFF OFF
DL3 OFF OFF OFF OFF OFF
DL4 OFF OFF OFF OFF OFF
DCF 100 100 100 100 100
CON 19 19 19 19 19
COF 7 7777
EL
Will display evaporator coil temp in real time every time an arrow is pressed.
DL
Will display discharge line temp in real time every time an arrow is pressed.
CB
Will display cabinet air temp in real time every time an arrow is pressed.
PLn
Will display power line voltage in real time every time an arrow is pressed.
RCO
Turns ON/OFF the compressor relay for 10-seconds or until an arrow is pressed.
RdF
Turns ON/OFF the defrost relay for 10-seconds or until an arrow is pressed.
RFA
Turns ON/OFF the blower relay for 10-seconds or until an arrow is pressed.
RDH
Turns ON/OFF the door heater triac for 10-seconds or until an arrow is pressed.
PRO Set the controller in receiving mode for programming.
CEP Clear all controller memories and reloads the factory default parameters.
REF
Firmware revision in the format X9.9 (X=version, 9=major revision, 9=minor revision).