Conair MPA Refrigerator User Manual


 
SPECIFICATIONS: MPW (WATER COOLED)
microKool Portable Chillers UGH004/0999
2-6 DESCRIPTION
MODEL MPW-1.5 MPW-2 MPW-3 MPW-4 MPW-5 MPW-7.5 MPW-10
Performance characteristics
Capacity {tons}
*
1.4 1.8 3.1 4.1 4.8 7.6 10.2
Compressor Hp {kW} 1.5 {1.12} 2 {1.49} 3 {2.24} 4 {2.98} 5 {3.73} 7.5 {5.59} 10 {7.45}
Pump Hp {kW}
0.33 {0.246} 0.50 {0.373} 0.75 {0.559} 1.5 {1.12} 1.5 {1.12} 1.5 {1.12} 1.5 {1.12}
Chilled water flow gpm {l/min}
3.4 {12.9} 4.5 {17.0} 7.5 {28.3} 9.9 {37.5} 11.4 {43.2} 18.2 {68.9} 24.5 {81.0}
Chilled water pressure psi {bar}
§
20 {1.4} 26 {1.8} 34 {2.3} 38 {2.6} 38 {2.6} 37.5 {2.6} 37 {2.5}
Reservoir capacity gal (l) 10 {37.9} 10 {37.9} 10 {37.9} 30 {114} 30 {114} 30 {114} 30 {114}
Condenser water flow gpm {l/min} 4.3 {16.3} 5.6 {21.2} 9.4 {35.6} 12.4 {47.0} 14.3 {54.2} 22.8 {86.4} 30.6 {116.0}
Dimensions inches {mm}
A - Height
**
45 {1143} 45 {1143} 45 {1143} 56 {1422} 56 {1422} 70 {1778} 70 {1778}
B - Depth 32 (812} 32 {812} 32 {812} 48 {812} 48 {812} 48 {812} 48 {812}
C - Width 29 {737} 29 {737} 29 {737} 34 {737} 34 {737} 34 {737} 34 {737}
Weight lb {kg}
Shipping weight 550 {249} 755 {342} 755 {342} 1010 {458} 1010 {458} 1250 {567} 1250 {567}
Installed weight 420 {190} 585 {265} 585 {265} 840 {381} 840 {381} 1080 {490} 1080 {490}
Utility requirements
Water connections NPT (female) inches 1 1 1 1.5 1.5 1.5 1.5
Process and condenser water inches 1 1 1 1.5 1.5 1.5 1.5
Voltages running and full load amps run full run full run full run full run full run full run full
208V/3 phase/60hz 8.8 15.5 13.7 15.9 17.7 22.3 23.9 28.3 27.0 30.5 34.9 41.5 44.2 50.8
230V/3 phase/60hz 8.0 14.0 12.4 14.4 16.0 20.2 21.6 25.6 24.4 27.6 31.6 37.6 40.0 46.0
460V/3 phase/60hz 4.0 7.0 6.2 7.2 8.0 10.1 10.8 12.8 12.2 13.8 15.8 18.8 20.0 23.0
575V/3 phase/60hz 3.2 5.6 5.0 5.8 6.4 8.1 8.6 10.2 9.8 11.0 12.6 15.0 16.0 18.4
Flow Rate (gpm)
Pressure (psi)
SPECIFICATION NOTES
* Based on 50° F (10° C) water temperature (100% water) leaving the chiller, standard pump selections, 85° F (27° C) condenser water supply
@ 25 psi minimum. Consult factory for other conditions.
Standard pump selection. Larger pumps available as options.
Based on 50° F water temperature leaving the chiller and 60° F (15° C) water temperature returning to the chiller.
§
Pressure at pump discharge.
** Control can be extended upward approximately 11 inches, which may or may not increase the overall height of the unit.
Specifications may change without notice. Check with a Conair representative for the most current information.
60 HZ PUMP PERFORMANCE CURVES