Conair MPA Refrigerator User Manual


 
SHUT DOWN
ALARMS
microKool Portable Chillers UGH004/0999
6-8 TROUBLESHOOTING
Alarm
Refrigerant pressure
is either too low or
too high.
WARNING:
The microKool should
be tested and repaired
only by qualified techni-
cians equipped with the
correct tools and
trained in the mainte-
nance and repair of
electrical and refriger-
ant systems used in
industrial applications.
Possible cause
Low refrigerant pressure:
Is the refrigerant charge
low?
Is the liquid refrigerant
line restricted?
High r
efrigerant pressure
Has the water or air flow
through the condenser
become restricted?
(Continued on next page)
Solution
See
C
HECKING
R
EFRIGERANT
C
HARGE
.
Check for leaks in the
refrigerant circuit. Contact a
certified refrigerant technician
to repair and recharge the sys-
tem.
Check for closed valves or a
plugged refrigerant line.
Verify that the liquid line
shut-off valve is open.
Verify that the suction valve
at the compressor is open.
Verify that the expansion
valve is working properly.
Check for closed valves and
obstructions, contaminants or
dirt that may have blocked or
restricted condenser efficiency.
All models:
Clean the condenser coils. See
C
LEANING
C
ONDENSERS
.
Air-cooled units:
Remove any obstructions to air
flow at the condenser air inlet
and outlet.
Verify that the condenser fans
are working. Confirm proper
rotation and check for an elec-
trical overload.
Water-cooled units:
Check for closed valves or
plugged water supply lines.
Verify that the condenser water
supply is working and that
incoming water pressure is at
least 25 psi.
Refrigerant Pressure
The chiller has detected a problem that could lead to equipment
damage or personal injury if it is not corrected.
The Alarm LED lights and the STOP/RUN LED flashes red.
The chiller turns off the compressor, but normal operation
resumes after you clear the alarm or the problem corrects itself.
The control displays a red LED or alarm code indicating the
source of the problem.