Conair MPA Refrigerator User Manual


 
SPECIFICATIONS:MPA (AIR COOLED)
UGH004/0999 microKool Portable Chillers
DESCRIPTION 2-7
MODEL MPA-1.5 MPA-2 MPA-3 MPA-4 MPA-5 MPA-7.5 MPA-11
Performance characteristics
Capacity {tons}
*
1.2 1.7 2.7 3.5 4.1 6.9 10.2
Compressor Hp {kW} 1.5 {1.12} 2.25 {2.05} 3.25 { 279.7} 4 {2.98} 5 {3.73} 9 {6.71} 12 {8.95}
Pump Hp (kW)
0.33 {0.246} 0.50 {0.373} 0.75 {0.559} 1.5 {1.12} 1.5 {1.12} 1.5 {1.12} 1.5 {1.12}
Chilled water flow gpm {l/min}
2.8 {10.6} 4.2 {15.9} 6.4 {24.2} 8.5{32.1} 9.9 {37.5} 16.6 {62.8} 24.5 {92.7}
Chilled water pressure psi {bar}
§
20 {1.4} 26 {1.8} 34 {2.3} 38 {2.6} 38 {2.6} 37.5 {2.6} 37 {2.5}
Reservoir capacity gal {l} 10 {37.9} 30 {114} 30 {114} 30{ 114} 30 {114} 30 {114} 40.5 {153}
Number of condenser fans 1 2 2 2 2 2 4
Condenser fan power Hp {kW} 0.063 {0.047} 0.063 {0.047} 0.063 {0.047} 0.063 {0.047} 0.063 {0.047} 0.50 {0.047} 0.50 {0.047}
Condenser air flow ft
3
/min {l/min} 1050 {496} 1704 {804} 2420 {1142} 4237 {2000} 4237 {2000} 5300 {2501} 8400 {3964}
Dimensions inches {mm}
A - Height
**
45 {1143} 48 {1129} 48 {1129} 56 {1422} 56 {1422} 70 {1778} 76 {1930}
B - Depth 32 {812} 44 {1118} 44 {1118} 48 {1219} 48 {1219} 48 {1219} 48 {1219}
C - Width 29 {737} 29 {737} 29 {737} 34 {737} 34 {737} 34 {737} 40{1016}
Weight lb {kg}
Shipping weight 750 {340} 1000 {454} 1000 {454} 1200 {544} 1200 {544} 1400 {635} 1600 {726}
Installed weight 610 {277} 830 {376} 830 {376} 1030 {467} 1030 {467} 1230 {558} 1430 {649}
Utility Requirements
Water connections NPT (female) inches 1 1 1 1.5 1.5 1.5 1.5
Process water inches 1 1 1 1.5 1.5 1.5 1.5
Voltages running and full load amps run full run full run full run full run full run full run full
208V/3 phase/60hz 11.7 18.3 16.1 18.6 21.0 27.0 27.8 32.3 31.0 34.5 63.0 69.6 90.8 97.8
230V/3 phase/60hz 10.6 16.6 14.6 16.8 19.0 24.4 25.2 29.2 28.0 31.2 57.0 63.0 82.2 88.5
460V/3 phase/60hz 5.3 8.3 7.3 8.4 9.5 12.2 12.6 14.6 14.0 15.6 28.5 31.5 41.1 44.3
575V/3 phase/60hz 4.2 6.6 5.8 6.7 7.6 9.8 10.1 11.7 11.2 12.5 22.8 25.2 32.9 35.4
SPECIFICATION NOTES
* Based on 50° F (10° C) water temperature (100% water) leaving the chiller, standard pump selections, 95° F (35° C) ambient air conditions.
Consult factory for other conditions.
Standard pump selection. Larger pumps available as options.
Based on 50° F water temperature leaving the chiller 60° F (15° C) water temperature returning to the chiller.
§
Pressure at pump discharge.
** Control can be extended upward approximately 11 inches, which may or may not increase the overall height of the unit.
Specifications may change without notice. Check with a Conair representative for the most current information.
Flow Rate (gpm)
60 HZ PUMP PERFORMANCE CURVES
Pressure (psi)